The Joint Adequacy of AGC and Primary Frequency Response in Single Balancing Authority Systems

被引:36
作者
Chavez, Hector [1 ]
Baldick, Ross [2 ]
Matevosyan, Julija [3 ]
机构
[1] Univ Santiago, Ingn Elect, Santiago, Chile
[2] Univ Texas Austin, Elect & Comp Engn Dept, Austin, TX 78712 USA
[3] ERCOT, Taylor, TX 76574 USA
基金
美国国家科学基金会;
关键词
Primary and secondary frequency control; power system dynamics; power system simulation; wind power generation; AUTOMATIC-GENERATION CONTROL; GOVERNOR DEADBAND; MARKET DESIGNS; PART I; MODE;
D O I
10.1109/TSTE.2015.2417315
中图分类号
X [环境科学、安全科学];
学科分类号
083001 [环境科学];
摘要
This paper generalizes previous work on automatic generation control (AGC) gain in a single balancing authority system. In previous work, a control performance standard 1 (CPS1)-compliant AGC gain for a single balancing authority interconnection was proposed, assuming that frequency response can be decoupled from AGC dynamics by widening governor dead bands. However, current practices suggest that widening dead bands may not be a wise course to take as it may deteriorate primary frequency response. This paper formulates sufficient conditions for the adequacy of the joint operation of AGC control and primary frequency response to be consistent with frequency response adequacy. Historical data and a simulation of ERCOT are presented to show numerical results.
引用
收藏
页码:959 / 966
页数:8
相关论文
共 26 条
[1]
[Anonymous], 1952, Mathematical Sbornik
[2]
Bilke T., 2013, BAL0031
[3]
LIMIT-CYCLE ANALYSIS OF A HYDROELECTRIC SYSTEM - A NEW APPROACH [J].
CHANG, HC ;
PAN, CT ;
WEI, CC ;
HUANG, CL .
ELECTRIC POWER SYSTEMS RESEARCH, 1986, 11 (01) :49-58
[4]
CPS1 Compliance-Constrained AGC Gain Determination for a Single-Balancing Authority [J].
Chavez, Hector ;
Baldick, Ross ;
Matevosyan, Julija .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (03) :1481-1488
[5]
Governor Rate-Constrained OPF for Primary Frequency Control Adequacy [J].
Chavez, Hector ;
Baldick, Ross ;
Sharma, Sandip .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (03) :1473-1480
[6]
Regulation Adequacy Analysis Under High Wind Penetration Scenarios in ERCOT Nodal [J].
Chavez, Hector ;
Baldick, Ross ;
Sharma, Sandip .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2012, 3 (04) :743-750
[7]
EirGrid, 2012, RAT CHANG FREQ DS3 A
[8]
EirGrid SONI., 2011, RAT CHANG FREQ DS3 A
[9]
Market Designs for the Primary Frequency Response Ancillary Service-Part II: Case Studies [J].
Ela, Erik ;
Gevorgian, Vahan ;
Tuohy, Aidan ;
Kirby, Brendan ;
Milligan, Michael ;
O'Malley, Mark .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (01) :432-440
[10]
Market Designs for the Primary Frequency Response Ancillary Service-Part I: Motivation and Design [J].
Ela, Erik ;
Gevorgian, Vahan ;
Tuohy, Aidan ;
Kirby, Brendan ;
Milligan, Michael ;
O'Malley, Mark .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (01) :421-431