A new PMU-based fault location algorithm for series compensated lines

被引:119
作者
Yu, CS [1 ]
Liu, CW
Yu, SL
Jiang, JA
机构
[1] Natl Taiwan Univ, Dept Elect Engn, Taipei 10764, Taiwan
[2] Natl Taiwan Sci & Technol, Dept Elect Engn, Taipei, Taiwan
[3] Private Kuang Wu Inst Technol & Commerce, Dept Elect Engn, Taipei, Taiwan
关键词
FACTS; series compensation; synchronized phasor measurement units;
D O I
10.1109/61.974185
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 [电气工程]; 0809 [电子科学与技术];
摘要
This paper presents a new fault location algorithm based on phasor measurement units (PMUs) for series compensated lines. Traditionally, the voltage drop of series device is computed by the device model in the fault locator of series compensated lines, but using this approach errors are induced by the inaccuracy of the series device model or the uncertainty operation mode of the series device. The proposed algorithm does not utilize the series device model and knowledge of the operation mode of the series device to compute the voltage drop during the fault period. Instead, the proposed algorithm uses two-step algorithm prelocation step and correction step, to calculate the voltage drop and fault location. The proposed technique can be easily applied to any series FACTS compensated line. EMTP generated data using a 30-km 34-kV transmission line has been used to test the accuracy of the proposed algorithm. The tested cases include various fault types, fault locations, fault resistances, fault inception angles, etc. The study also considers the effect of various operation modes of the compensated device during the fault period. Simulation results indicate that the proposed algorithm can achieve up to 99.95% accuracy for most tested cases.
引用
收藏
页码:33 / 46
页数:14
相关论文
共 19 条
[1]
PROTECTION SYSTEM REPRESENTATION IN THE ELECTROMAGNETIC TRANSIENTS PROGRAM [J].
CHAUDHARY, AKS ;
TAM, KS ;
PHADKE, AG .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (02) :700-&
[2]
Christi N., 1991, IEE INT C, P33
[3]
Dommel H.W., 1986, ELECTROMAGNETIC TRAN
[4]
Method to improve digital distance relay impedance measurement when used in series compensated lines protected by a metal oxide varistor [J].
Ghassemi, F ;
Goodarzi, J ;
Johns, AT .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1998, 145 (04) :403-408
[5]
An adaptive protection scheme for Advanced Series Compensated (ASC) transmission lines [J].
Girgis, AA ;
Sallam, AA ;
El-Din, AK .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (02) :414-420
[6]
A LINEARIZED MODEL FOR MOV-PROTECTED SERIES CAPACITORS [J].
GOLDSWORTHY, DL .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1987, 2 (04) :953-958
[7]
GROSS CA, 1986, POWER SYSTEM ANAL
[8]
A novel non-unit protection for series compensated EHV transmission lines based on fault generated high frequency voltage signals [J].
Jayasinghe, JASB ;
Aggarwal, RK ;
Johns, AT ;
Bo, ZQ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (02) :405-413
[9]
Jiang JA, 2000, IEEE T POWER DELIVER, V15, P486
[10]