Effect of pollution distribution class on insulators flashover under AC voltage

被引:23
作者
Boudissa, R. [1 ]
Bayadi, A. [2 ]
Baersch, R. [3 ]
机构
[1] Univ A Mira, Lab Genie Elect, Bejaia, Algeria
[2] Univ Ferhat Abbas, Dept Electrotech, Setif, Algeria
[3] FG Hochspannungstech, Hsch Zittau Gorlitz, Zittau, Germany
关键词
Insulators; Pollution distribution; Leakage current; Flashover voltage;
D O I
10.1016/j.epsr.2013.06.009
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The aim of this paper concerns the effect of pollution distribution class on insulators flashover under AC voltage. Three scenarios of non-uniform pollution distribution were studied: transversal, longitudinal periodic and longitudinal non-periodic. These scenarios are commonly seen in the field with in-service insulators located near polluting sources and at sites with prevailing winds. In the first scenario, the flashover voltage of polluted insulators under non-uniform transversal distribution is 21% higher than that under uniform contamination. In such a case, the insulator can withstand the voltage stresses much better than under uniform contamination conditions. The flashover voltage of an insulating surface under periodic longitudinal pollution distribution is at maximum 30% lower than that obtained in the same insulation in the case of a uniform contamination. The third scenario has shown the existence of a minimum flashover voltage which is 42% lower than that obtained in a uniform distribution. Laboratory tests revealed that the minimum flashover voltage can be attributed to the maximum shortening of the weakly polluted creepage distance of the insulator before its full flashover. In a so unfavorable situation, it will be necessary either to proceed to a re-dimensioning of the insulation based on their performance under non-uniform contamination or take preventive measures of pollution control of the insulators. (c) 2013 Elsevier B.V. All rights reserved.
引用
收藏
页码:176 / 182
页数:7
相关论文
共 17 条
[1]   PERFORMANCE OF HV TRANSMISSION-LINE INSULATORS IN DESERT CONDITIONS .3. POLLUTION MEASUREMENTS AT A COASTAL SITE IN THE EASTERN REGION OF SAUDI-ARABIA [J].
AKBAR, M ;
ZEDAN, F .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (01) :429-438
[2]  
[Anonymous], 2000, ELECTRA, P55
[3]  
[Anonymous], 1992, ELECTRA, P99
[4]  
Beroual A, 2002, 2002 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, P331, DOI 10.1109/CEIDP.2002.1048802
[5]   Effect of insulator shape on surface discharges and flashover under polluted conditions [J].
Boudissa, R ;
Djafri, S ;
Haddad, A ;
Belaicha, R ;
Bearsch, R .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2005, 12 (03) :429-437
[6]  
Boudissa R., 2005, 14 ISH TSINGH U AOUT
[7]  
Naito K., 1989, IEEE MEX SECT M JUL
[8]  
Pilling J., 1991, Seventh International Symposium on High Voltage Engineering, P211
[9]  
Rayes M. N., 1991, 7 INT S HV ENG DRESD
[10]   MODELING OF HVDC WALL BUSHING FLASHOVER IN NONUNIFORM RAIN [J].
RIZK, FAM ;
KAMEL, SI .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (04) :1650-1662