Extinction limit of a pool fire with a water mist

被引:61
作者
Kim, MB [1 ]
Jang, YJ [1 ]
Yoon, MO [1 ]
机构
[1] MYOUNGJI UNIV,DEPT ARCHITECTURE,YONGIN 449728,KYUNGI PROVINCE,SOUTH KOREA
关键词
D O I
10.1016/S0379-7112(97)00011-8
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This work describes an experimental investigation of fire extinction limit and enhancement for a gasoline pool fire interacting with a water mist. A downward-directed nozzle produces a fine water spray over a small-scale opposed pool fire. The fire extinction limit is obtained from minimum nozzle injection pressure measured when the fire extinguish takes place. The burning rare of the fuel is also measured using a verified technique. For the conditions tested, it is shown that there are two distinct regions in the relationship between the distance from the nozzle to the fuel pan and the injection pressure, i.e. a fire extinction region and a fire enhanced region. The effective water flux is shown to be a more useful parameter than the injection pressure for the fire extinction limit. It is also revealed that the larger the spray thrust the larger the burning rate is in the fire enhanced region. (C) 1997 Elsevier Science Ltd.
引用
收藏
页码:295 / 306
页数:12
相关论文
共 9 条
[1]  
Alpert R.L., 1993, WAT MIST FIR SUPPR W, P31
[2]  
Andrew S., 1993, 93009 CAA FIR RES ST
[3]   Interaction of a water mist with a buoyant methane diffusion flame [J].
Downie, B ;
Polymeropoulos, C ;
Gogos, G .
FIRE SAFETY JOURNAL, 1995, 24 (04) :359-381
[4]  
Hill R., 1993, P WAT MIST FIR SUPPR, P93
[5]   Burning rate of a pool fire with downward-directed sprays [J].
Kim, MB ;
Jang, YJ ;
Kim, JK .
FIRE SAFETY JOURNAL, 1996, 27 (01) :37-48
[6]  
KIM MB, 1995, P 6 INT S TRANSP PHE, V2, P529
[7]  
National Fire Protection Association, 1996, 750 NFPA
[8]   A MODEL OF FREELY BURNING POOL FIRES [J].
NDUBIZU, CC ;
RAMAKER, DE ;
TATEM, PA ;
WILLIAMS, FW .
COMBUSTION SCIENCE AND TECHNOLOGY, 1983, 31 (5-6) :233-247
[9]  
RYDEMAN A, 1991, R30080 SNTRI