The results of an analytic investigation on the influence of the thermal conductance of a sorption element (adsorber/desorber), evaporator, and condenser on the performance of a three-bed silica-gel-water adsorption chiller are presented with consideration given to the thermal capacitance ratio of the adsorbent and metal of the adsorber/desorber heat exchanger. The analysis was performed by using a cycle-simulation model developed by the authors. The chiller is driven by exploiting waste heat at a temperature 60 and 95 degrees C with a cooling source at 30 degrees C for air conditioning purpose. The results show that the cycle performance is strongly affected by the thermal capacitance ratio and sorption element thermal conductance due to several sensible heating/cooling requirements resulting from batched cycle operation. The model is somewhat sensitive to the thermal conductance of the evaporator, and the thermal conductance of the condenser is the least sensitive parameter.
引用
收藏
页码:80 / 87
页数:8
相关论文
共 10 条
[1]  
BEIJER HA, 1994, P INT ABS HEAT PUMP, V31, P457
[2]  
Boelman EC, 1995, ASHRAE TRAN, V101, P358
[3]   Multi-bed regenerative adsorption chiller - improving the utilization of waste heat and reducing the chilled water outlet temperature fluctuation [J].
Chua, HT ;
Ng, KC ;
Malek, A ;
Kashiwagi, T ;
Akisawa, A ;
Saha, BB .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2001, 24 (02) :124-136
[4]   PREDICTIVE MODEL AND EXPERIMENTAL RESULTS FOR A 2-ADSORBER SOLID ADSORPTION HEAT-PUMP [J].
DOUSS, N ;
MEUNIER, FE ;
SUN, LM .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 1988, 27 (02) :310-316
[5]  
GUILLEMINOT JJ, 1993, P INT ABSORPTION HEA, V31, P401
[6]  
Kashiwagi T.J.A.T, 1997, ASHRAE T, V103, P50
[7]  
Meunier F., 1978, CAHIERS AFEDES, V5, P57
[8]  
Ng K. C., 2003, T JSRAE, V20, P429
[9]   Performance evaluation of a low-temperature waste heat driven multi-bed adsorption chiller [J].
Saha, BB ;
Koyama, S ;
Lee, JB ;
Kuwahara, K ;
Alam, KCA ;
Hamamoto, Y ;
Akisawa, A ;
Kashiwagi, T .
INTERNATIONAL JOURNAL OF MULTIPHASE FLOW, 2003, 29 (08) :1249-1263
[10]  
Saha BB, 1995, ASHRAE TRAN, V101, P348