Analysis and Mitigation of Low-Frequency Instabilities in Autonomous Medium-Voltage Converter-Based Microgrids With Dynamic Loads

被引:149
作者
Kahrobaeian, Alireza [1 ]
Mohamed, Yasser Abdel-Rady I. [1 ]
机构
[1] Univ Alberta, Dept Elect & Comp Engn, Edmonton, AB T6G2V4, Canada
关键词
Decentralized droop control; distributed generation microgrids; dynamic loads; induction motor (IM); stability; PARALLEL OPERATION; ENERGY MANAGEMENT; INVERTERS; STABILITY; GENERATION; SENSOR; AC;
D O I
10.1109/TIE.2013.2264790
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The microgrid concept is gaining widespread acceptance in near-term future power networks. Medium-voltage (MV) microgrids can be subjected to a high penetration level of dynamic loads [e. g., induction motor (IM) loads]. The highly nonlinear IM dynamics that couple active power, reactive power, voltage, and supply frequency dynamics challenge the stability of MV droop-controlled microgrids. However, detailed analysis and, more importantly, stabilization of MV microgrids with IM loads, are not reported in current literature. To fill in this gap, this paper presents integrated modeling, analysis, and stabilization of MV droop-controlled microgrids with IM load. A detailed small-signal model of a typical MV droop-controlled microgrid system, which is based on the IEEE Standard 399, with both dynamic and static loads is developed. The proposed model accounts for the impact of supply frequency dynamics associated with the droop-control scheme to accurately link the microgrid frequency dynamics to the motor dynamics. To stabilize the microgrid system in the presence of IM loads, a 2-degree-of-freedom active damping controller is proposed to stabilize the newly introduced oscillatory dynamics. The proposed supplementary active damping controller does not interfere with the steady-state performance, and yields robust control performance under a wide range of droop parameters and robust damping performance at small-and large-signal disturbances. A theoretical analysis, simulation, and experimental results are presented to show the effectiveness of the proposed control scheme.
引用
收藏
页码:1643 / 1658
页数:16
相关论文
共 26 条
[1]  
[Anonymous], 1994, POWER SYSTEM STABILI
[2]  
[Anonymous], 2011, INT ENERGY AGENCY, DOI DOI 10.1787/20792581
[3]   Control for Grid-Connected and Intentional Islanding Operations of Distributed Power Generation [J].
Balaguer, Irvin J. ;
Lei, Qin ;
Yang, Shuitao ;
Supatti, Uthane ;
Peng, Fang Zheng .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (01) :147-157
[4]   Energy Management in Autonomous Microgrid Using Stability-Constrained Droop Control of Inverters [J].
Barklund, E. ;
Pogaku, Nagaraju ;
Prodanovic, Milan ;
Hernandez-Aramburo, C. ;
Green, Tim C. .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (05) :2346-2352
[5]   Direct torque control of an induction motor using a single current sensor [J].
Bertoluzzo, M ;
Buja, G ;
Menis, R .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2006, 53 (03) :778-784
[6]   Multiobjective Intelligent Energy Management for a Microgrid [J].
Chaouachi, Aymen ;
Kamel, Rashad M. ;
Andoulsi, Ridha ;
Nagasaka, Ken .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (04) :1688-1699
[7]   Small-signal stability for parallel-connected inverters in stand-alone AC supply systems [J].
Coelho, EAA ;
Cortizo, PC ;
Garcia, PFD .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2002, 38 (02) :533-542
[8]   Decentralized Parallel Operation of Inverters Sharing Unbalanced and Nonlinear Loads [J].
De, Dipankar ;
Ramanarayanan, Venkataramanan .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2010, 25 (12) :2995-3025
[9]   Voltage oscillatory instability caused by induction motor loads [J].
deMello, FP ;
Feltes, JW .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (03) :1279-1284
[10]   Composite Loads in Stand-Alone Inverter-Based Microgrids-Modeling Procedure and Effects on Load Margin [J].
Diaz, Guzman ;
Gonzalez-Moran, Cristina ;
Gomez-Aleixandre, Javier ;
Diez, Alberto .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2010, 25 (02) :894-905