Decision analysis on fire safety design based on evaluating building fire risk to life

被引:34
作者
Chu, Guanquan [1 ,2 ]
Sun, Jinhua [2 ]
机构
[1] Minist Commun, Waterborne Transportat Inst, Beijing 100088, Peoples R China
[2] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230026, Anhui, Peoples R China
关键词
decision analysis; risk assessment; building fires; uncertainty; evacuation;
D O I
10.1016/j.ssci.2007.06.011
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This study presents a framework of decision analysis on fire safety design alternatives based on evaluating building fire risk to life. A probabilistic risk assessment method for occupant life is presented with consideration of some uncertainties of evacuation process and fire development at first. For occupant evacuation time assessment, occupant pre-movement time is characterized by normal distribution. For onset time to untenable conditions assessment, its uncertainty is considered as probability distribution according to the range of design fires. Based on event tree technique, probable fire scenarios are analyzed with consideration of the effect of fire protection systems, employees extinguishing, etc. It is difficult to make a precise assessment on probability and consequence of every fire scenario, but their lower bound and upper bound can be achieved based on statistical data. Therefore, Supersoft Decision Theory [Malmnas, P.E., 1995. Methods of Evaluation in Supersoft Decision Theory. Department of Philosophy, Stockholm University, 365 Stockholm; Johansson, H., Malmnas, P.E., 2000. Application of supersoft decision theory in fire risk assessment. Journal of Fire Protection Engineering 14, 55-84] that allows decision maker to utilize vague statement is utilized to integrate with risk assessment to make decision on different fire safety design alternatives. To express how to make decision on different fire safety design alternatives based on evaluating building fire risk to life, two hypothetical fire safety design alternatives for a commercial building are presented. (C) 2007 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1125 / 1136
页数:12
相关论文
共 37 条
  • [1] [Anonymous], 2005, 1471 NIST
  • [2] [Anonymous], DD240 BS
  • [3] Ashe B, 1999, FIRE MATER, V23, P333, DOI 10.1002/(SICI)1099-1018(199911/12)23:6<333::AID-FAM707>3.0.CO
  • [4] 2-2
  • [5] Benichou N, 2005, J FIRE PROT ENG, V15, P145, DOI [10.1177/1042391505049437, DOI 10.1177/1042391505049437]
  • [6] Bensilum M, 2002, P 7 INT S FIR SAF SC, P941
  • [7] BUKOWSKI RW, 1999, P 3 INT C FIR RES EN, P87
  • [8] Charters D., 2002, P 7 INT S FIR SAF SC, P357
  • [9] CHEN T, 2004, THESIS U SCI TECHNOL
  • [10] The effect of pre-movement time and occupant density on evacuation time
    Chu, GQ
    Sun, JH
    [J]. JOURNAL OF FIRE SCIENCES, 2006, 24 (03) : 237 - 259