Fourier and walsh digital filtering algorithms for distance protection

被引:32
作者
Altuve, HJ
Diaz, I
Vazquez, E
机构
[1] Universidad Autönoma de Nuevo Leon, Programa Doctoral en Ingenieria Eléctrica, P.O. Box F-150
关键词
D O I
10.1109/59.486133
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Filtering requirements for distance relays are very critical, because they must estimate precisely and quickly the electrical distance to the fault, even with highly distorted input signals. A number of digital filtering algorithms for distance relays have been proposed and some of them are in use in practical relays; however, power system evolution increases the corruption level of signals and imposes the necessity of continuing the research efforts in this area. In the present paper a comparative evaluation of different digital filtering algorithms for distance protection is performed. An evaluation method is proposed, which gives a comprehensive information about filter transient behavior on a wide frequency range of noise. The discussion is focused in well-known algorithms based on Fourier and Walsh transforms, and includes a recently proposed combined sine-cosine filter.
引用
收藏
页码:457 / 462
页数:6
相关论文
共 9 条
[1]  
ALTUVE HJ, 1994, 7 REUN VER POT IEEE
[2]  
ALTUVE HJ, 1993, 2 S IB PROT SIST EL, P215
[3]   MODELING OF FAULT-INDUCED NOISE SIGNALS FOR COMPUTER RELAYING APPLICATIONS [J].
GIRGIS, AA ;
BROWN, RG .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (09) :2834-2841
[4]  
Horton J. W., 1975, IEEE PUBLICATION, P1
[5]  
LUCKETT RG, 1975, IEE C PUBLICATION, V125, P252
[6]   A NEW COMPUTER-BASED FLUX-RESTRAINED CURRENT-DIFFERENTIAL RELAY FOR POWER TRANSFORMER PROTECTION [J].
PHADKE, AG ;
THORP, JS .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (11) :3624-3629
[7]  
Ramamoorty M., 1972, Journal of the Institution of Engineers (India) Electrical Engineering Division, V52, P235
[8]  
Schweitzer E. O., 1992, 19 ANN W PROT REL C
[9]  
SCHWEITZER EO, 1977, IEEE PES SUMM M MEX