Multiple faults diagnosis for sensors in air handling unit using Fisher discriminant analysis

被引:77
作者
Du, Zhimin [1 ]
Jin, Xinqiao [1 ]
机构
[1] Shanghai Jiao Tong Univ, Sch Mech Engn, Shanghai 200240, Peoples R China
基金
中国博士后科学基金;
关键词
Multiple faults; Principal component analysis; Fisher discriminant analysis; Air handling unit; Detection and diagnosis;
D O I
10.1016/j.enconman.2008.06.032
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents a data-driven method based on principal component analysis and Fisher discriminant analysis to detect and diagnose multiple faults including fixed bias, drifting bias, complete failure of sensors, air damper stuck and water valve stuck occurred in the air handling units. Multi-level strategies are developed to improve the diagnosis efficiency. Firstly, system-level PCA model I based on energy balance is used to detect the abnormity in view of system. Then the local-level PCA model A and B based on supply air temperature and outdoor air flow rate control loops are used to further detect the occurrence of faults and pre-diagnose them into various locations. As a linear dimensionality reduction technique, moreover, Fisher discriminant analysis is presented to diagnose the fault source after pre-diagnosis. With Fisher transformation, all of the data classes including normal and faulty operation can be re-arrayed in a transformed data space and as a result separated. Comparing the Mahalanobis distances (MDs) of all the candidates, the least one can be identified as the fault source. (c) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:3654 / 3665
页数:12
相关论文
共 31 条
[1]  
[Anonymous], ASHRAE T
[2]  
[Anonymous], 2001, PATTERN CLASSIFICAT
[3]   Fault diagnosis in chemical processes using Fisher discriminant analysis, discriminant partial least squares, and principal component analysis [J].
Chiang, LH ;
Russell, EL ;
Braatz, RD .
CHEMOMETRICS AND INTELLIGENT LABORATORY SYSTEMS, 2000, 50 (02) :243-252
[4]   Fault diagnosis based on Fisher discriminant analysis and support vector machines [J].
Chiang, LH ;
Kotanchek, ME ;
Kordon, AK .
COMPUTERS & CHEMICAL ENGINEERING, 2004, 28 (08) :1389-1401
[5]  
Comstock M.C., 1999, HL9920 PURD U RW HER
[6]   Fault diagnosis in air-conditioning systems: A multi-step fuzzy model-based approach [J].
Dexter, AL ;
Ngo, D .
HVAC&R RESEARCH, 2001, 7 (01) :83-102
[7]  
DEXTER P, 2001, DEMONSTRATING AUTOMA
[8]   Fault detection and diagnosis based on improved PCA with JAA method in VAV systems [J].
Du, Zhimin ;
Jin, Xinqiao ;
Wu, Lizhou .
BUILDING AND ENVIRONMENT, 2007, 42 (09) :3221-3232
[9]   Detection and diagnosis for sensor fault in HVAC systems [J].
Du, Zhimin ;
Jin, Xinqiao .
ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (03) :693-702
[10]   Joint diagnosis of process and sensor faults using principal component analysis [J].
Dunia, R ;
Qin, SJ .
CONTROL ENGINEERING PRACTICE, 1998, 6 (04) :457-469