Effectiveness of in-room air filtration and dilution ventilation for tuberculosis infection control

被引:108
作者
MillerLeiden, S
Lobascio, C
Nazaroff, WW
Macher, JM
机构
[1] UNIV CALIF BERKELEY, DEPT CIVIL & ENVIRONM ENGN, BERKELEY, CA 94720 USA
[2] ALENIA SPACE, TURIN, ITALY
[3] CALIF DEPT HLTH SERV, ENVIRONM HLTH LAB BRANCH, BERKELEY, CA USA
关键词
D O I
10.1080/10473289.1996.10467523
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Tuberculosis (TB) is a public health problem that may pose substantial risks to health care workers and others. TB infection occurs by inhalation of airborne bacteria emitted by persons with active disease. We experimentally evaluated the effectiveness of in-room air filtration systems, specifically portable air filters (PAFs) and ceiling-mounted air filters (CMAFs), in conjunction with dilution ventilation, for controlling TB exposure in high-risk settings. For each experiment, a test aerosol was continuously generated and released into a full-sized room. With the in-room air filter and room ventilation system operating, time-averaged airborne particle concentrations were measured at several points. The effectiveness of in-room air filtration plus ventilation was determined by comparing particle concentrations with and without device operation. The four PAFs and three CMAFs we evaluated reduced room-average particle concentrations, typically by 30% to 90%, relative to a baseline scenario with two air-changes per hour of ventilation (outside air) only. Increasing the rate of air flow recirculating through the filter and/or air flow from the ventilation did not always increase effectiveness. Concentrations were generally higher near the emission source than elsewhere in the room. Both the air flow configuration of the filter and its placement within the room were important, influencing room air flow patterns and the spatial distribution of concentrations. Air filters containing efficient, but non-high efficiency particulate air (HEPA) filter media were as effective as air filters containing HEPA filter media.
引用
收藏
页码:869 / 882
页数:14
相关论文
共 46 条
  • [1] *AM I ARCH COMM AR, 1987, GUID CONSTR EQ HOSP
  • [2] *AM SOC HEAT REFR, 1991, 1991 ASHRAE HDB HEAT
  • [3] BASS J, 1992, AM REV RESPIR DIS, V146, P1623
  • [4] TUBERCULOSIS - COMMENTARY ON A REEMERGENT KILLER
    BLOOM, BR
    MURRAY, CJL
    [J]. SCIENCE, 1992, 257 (5073) : 1055 - 1064
  • [5] PREVENTING THE NOSOCOMIAL TRANSMISSION OF TUBERCULOSIS
    BLUMBERG, HM
    WATKINS, DL
    BERSCHLING, JD
    ANTLE, A
    MOORE, P
    WHITE, N
    HUNTER, M
    GREEN, B
    RAY, SM
    MCGOWAN, JE
    [J]. ANNALS OF INTERNAL MEDICINE, 1995, 122 (09) : 658 - 663
  • [6] BRENNEN C, 1988, INFECT CONT HOSP EP, V9, P548, DOI 10.1086/645774
  • [7] NOSOCOMIAL TUBERCULOSIS
    CATANZARO, A
    [J]. AMERICAN REVIEW OF RESPIRATORY DISEASE, 1982, 125 (05): : 559 - 562
  • [8] Chen Q, 1992, Indoor Air, V2, P154, DOI DOI 10.1111/j.1600-0668.1992.04-23.x
  • [9] NOSOCOMIAL TRANSMISSION OF TUBERCULOSIS IN A HOSPITAL UNIT FOR HIV-INFECTED PATIENTS
    DOOLEY, SW
    VILLARINO, ME
    LAWRENCE, M
    SALINAS, L
    AMIL, S
    RULLAN, JV
    JARVIS, WR
    BLOCH, AB
    CAUTHEN, GM
    [J]. JAMA-JOURNAL OF THE AMERICAN MEDICAL ASSOCIATION, 1992, 267 (19): : 2632 - 2634
  • [10] CHARACTERIZATION OF CONTAMINANT CONCENTRATIONS IN ENCLOSED SPACES
    ESMEN, NA
    [J]. ENVIRONMENTAL SCIENCE & TECHNOLOGY, 1978, 12 (03) : 337 - 339