Three phase models of specially connected transformers

被引:46
作者
Chen, BK
Guo, BS
机构
[1] Tatung Institute of Technology, Taipei
关键词
D O I
10.1109/61.484031
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
To reduce the system imbalance, various types of specially-connected transformers have been adopted in Taiwan and abroad. Because three-phase transformer models are necessary for three-phase load flow simulation, specially-connected transformers which have been adopted so far are selected to derive three-phase models in this paper. These transformers include the single-phase connection, the V-V the Wye-Delta connection, the Scott the Le Blanc connection, and the Modified-Woodbridge connection. The three-phase models with the specially-connected transformers offered in this paper distinctly represent the HSR feeding system by means of the physical three-phase circuit and the symmetrical-component equivalent circuit. The three-phase model could be joined to the three-phase load flow program to exactly analyze the system imbalance in the future. The symmetrical-component equivalent circuit may also be used to derive the approximate unbalance-estimating formula.
引用
收藏
页码:323 / 330
页数:8
相关论文
共 13 条
[1]  
[Anonymous], THESIS
[2]  
ASTENGO G, 1989, IEE CONF PUBL, V312, P178
[3]  
BURKE JJ, 1983, EPRI EL3001 REP
[4]   ELECTRIFICATION OF TAIWAN MAIN-LINE RAILWAY FROM KEELUNG TO KAOHSIUNG [J].
CASE, SH ;
HAYES, AM ;
MCNEIL, JH ;
MORRISON, RE ;
RICHES, EE .
IEE PROCEEDINGS-B ELECTRIC POWER APPLICATIONS, 1983, 130 (05) :289-301
[5]  
DENLEY MR, 1987, IEE C PUBLICATION, V279, P189
[6]  
Howroyd D. C., 1984, IEE P B, V131, P226
[7]  
LI QZ, 1989, IEE CONF PUBL, V312, P222
[8]  
Methinier M., 1992, HIGH SPEED RAILWAY
[9]  
Mochinaga Y., 1990, Transactions of the Institute of Electrical Engineers Japan, Part D, V110-D, P570, DOI 10.1541/ieejias.110.570
[10]  
Mochinaga Y., 1991, Transactions of the Institute of Electrical Engineers Japan, Part D, V111-D, P237, DOI 10.1541/ieejias.111.237