A control method for the active power filter in unsymmetrical voltage systems

被引:15
作者
Komatsu, Y [1 ]
Kawabata, T [1 ]
机构
[1] Ritsumeikan Univ, Dept Elect & Elect Engn, Kusatsu, Siga 5258577, Japan
关键词
D O I
10.1080/002072199132789
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, the authors propose a calculation method for the compensating current reference of the active power filter, where a nonlinear load exists in a three-phase, three-wire unsymmetrical voltage system. This new method has been named the extension pq method. The authors have experimented with the extension pq method and the pq method, using the same current-controlled intelligent power module inverter for both methods. The results of the experiments proved that in the unsymmetrical voltage system the source current was distorted in the case of the pq method, but undistorted in the case of the extension pq method.
引用
收藏
页码:1249 / 1260
页数:12
相关论文
共 4 条
[1]   INSTANTANEOUS REACTIVE POWER COMPENSATORS COMPRISING SWITCHING DEVICES WITHOUT ENERGY-STORAGE COMPONENTS [J].
AKAGI, H ;
KANAZAWA, Y ;
NABAE, A .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1984, 20 (03) :625-630
[2]  
Komatsu Y., 1996, Proceedings of the ICHQP. 7th International Conference on Harmonics and Quality of Power, P1
[3]  
KOMATSU Y, 1995, P 6 EUR C POW EL APP, P1904
[4]  
KOMATSU Y, 1995, P PEDS C 95, V2, P583