Flow maldistribution in heat exchangers

被引:213
作者
Lalot, S [1 ]
Florent, P [1 ]
Lang, SK [1 ]
Bergles, AE [1 ]
机构
[1] EIPC, METIER, F-62967 Longuenesse, France
关键词
heat exchanger; electrical heater; fluid flow distribution; gross flow maldistribution; reverse flow; fluid flow homogenization;
D O I
10.1016/S1359-4311(98)00090-8
中图分类号
O414.1 [热力学];
学科分类号
摘要
Based on the study of gross flow maldistribution in an experimental electrical heater, this paper presents the effect of flow nonuniformity on the performance of heat exchangers. First, it is shown that it is much more important to understand maldistributions for electrical heaters than for two-fluid heat exchangers. The study of the flow distribution in a particular heater shows that reverse flows may occur for poor inlet header design. Suggested here is a simple way to homogenize the flow distribution and a simple law to calculate, with good accuracy, the velocity ratio (ratio of the highest velocity in the tubes to the lowest velocity). The original fluid distribution is applied to heat exchangers (condensers, counterflow and crossflow heat exchangers), and it is shown that gross flow maldistribution leads to a loss of effectiveness of about 7% for condensers and counterflow heat exchangers, and up to 25% for crossflow exchangers, for velocity ratios up to 15. (C) 1999 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:847 / 863
页数:17
相关论文
共 7 条
[1]  
Fraas A.P., 1989, HEAT EXCHANGER DESIG
[2]  
IDELCIK IE, 1969, MEMENTO PERTES CHARG
[3]  
Incropera F.P., 1990, FUNDAMENTALS HEAT MA
[4]  
LALOT S, 1994, THESIS U VALENCIENNE
[5]  
PADET J, 1991, FLUIDES ECOULEMENT M
[6]  
PADET J, 1994, ECHANGEURS THERMIQUE
[7]  
Rohsenow WM, 1985, Handbook of Heat Transfer