Fault tolerant control of outdoor air and AHU supply air temperature in VAV air conditioning systems using PICA method

被引:40
作者
Jin, Xinqiao [1 ]
Du, Zhimin [1 ]
机构
[1] Shanghai Jiao Tong Univ, Dept Mech Engn, Shanghai, Peoples R China
关键词
VAV systems; outdoor air; indoor humidity; fault tolerant control; principal component analysis;
D O I
10.1016/j.applthermaleng.2005.10.039
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents a fault tolerant control method to control the outdoor air ventilation and AHU supply air temperature, which concerned indoor air quality and humidity, respectively to satisfy ASHRAE Standard in VAV systems. The principal component analysis method, joint angle method, and compensatory reconstruction are used to detect, isolate, and reconstruct the fault, respectively for fault tolerant control. They are tested and evaluated in a simulation environment under the condition of temperature and flow sensors with fix bias faults. (C) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1226 / 1237
页数:12
相关论文
共 11 条
[1]  
ANN BC, 2001, ASHRAE T, V107, P839
[2]  
DEXTER AL, 2001, INT J HVAC R RES, V7, P83
[3]   Joint diagnosis of process and sensor faults using principal component analysis [J].
Dunia, R ;
Qin, SJ .
CONTROL ENGINEERING PRACTICE, 1998, 6 (04) :457-469
[4]   CONTROL PROCEDURES FOR RESIDUALS ASSOCIATED WITH PRINCIPAL COMPONENT ANALYSIS [J].
JACKSON, JE ;
MUDHOLKAR, GS .
TECHNOMETRICS, 1979, 21 (03) :341-349
[5]  
Stylianou M, 1996, ASHRAE TRAN, V102, P615
[6]   CO2-based occupancy detection for on-line outdoor air flow control [J].
Wang, SW ;
Jin, XQ .
INDOOR AND BUILT ENVIRONMENT, 1998, 7 (03) :165-181
[7]   AHU sensor fault diagnosis using principal component analysis method [J].
Wang, SW ;
Xiao, F .
ENERGY AND BUILDINGS, 2004, 36 (02) :147-160
[8]   Fault diagnosis with multivariate statistical models part I: using steady state fault signatures [J].
Yoon, SY ;
MacGregor, JF .
JOURNAL OF PROCESS CONTROL, 2001, 11 (04) :387-400
[9]  
[No title captured]
[10]  
[No title captured]