A new adaptive PMU based protection scheme for transposed/untransposed parallel transmission lines

被引:123
作者
Chen, CS [1 ]
Liu, CW
Jiang, JA
机构
[1] Natl Taiwan Univ, Dept Elect Engn, Taipei 10764, Taiwan
[2] Natl Taiwan Univ, Dept Bioind Mechatron Engn, Taipei 10764, Taiwan
关键词
computer relaying; digital protection; fault detection/location; parallel transmission lines; phasor measurement unit (PMU);
D O I
10.1109/61.997906
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 [电气工程]; 0809 [电子科学与技术];
摘要
This paper proposes a brand-new adaptive phasor measurement unit (PMU) based protection scheme for both transposed and untransposed parallel transmission lines. The development of the scheme is based on the distributed line model and the synchronized phasor measurements at both ends of lines. By means of eigenvalue/eigenvector theory to decouple the mutual coupling effects between parallel lines, the fault detection and location indices are derived. The two proposed indices are used in coordination such that the internal and external fault events can be distinguished completely. By on-line estimating the line parameters under the actual power system conditions, the proposed scheme will respond more accurately to power system faults. Extensive simulation results using EMTP have verified that the accuracy of the fault location achieved is up to 99.9%. The proposed protection system responds well and fast with regard to dependability and security. All the results show that the performance of the proposed detection/location indices is independent of fault types, locations, resistance, source impedance, fault inception angles, and load flows.
引用
收藏
页码:395 / 404
页数:10
相关论文
共 23 条
[1]
Some improvements in the three-phase differential, equation algorithm for fast transmission line protection [J].
Akke, M ;
Thorp, JT .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (01) :66-72
[2]
[Anonymous], 1995, Digital Protection for Power Systems
[3]
TRAVELING-WAVE-BASED PROTECTION OF DOUBLE-CIRCUIT LINES [J].
BOLLEN, MHJ .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1993, 140 (01) :37-47
[4]
DOMMEL H. W., 1992, EMTP THEORY BOOK
[5]
A new digital directional transverse differential, current protection technique [J].
Eissa, MM ;
Malik, OP .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (03) :1285-1291
[6]
A DIGITAL PROTECTION TECHNIQUE FOR PARALLEL TRANSMISSION-LINES USING A SINGLE RELAY AT EACH END [J].
GILANY, MI ;
MALIK, OP ;
HOPE, GS .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (01) :118-125
[7]
Jiang JA, 2000, IEEE T POWER DELIVER, V15, P486
[8]
Jiang JA, 2000, IEEE T POWER DELIVER, V15, P1136
[9]
ACCURATE FAULT LOCATION TECHNIQUE FOR POWER TRANSMISSION-LINES [J].
JOHNS, AT ;
JAMALI, S .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1990, 137 (06) :395-402
[10]
Adaptive distance protection of double-circuit lines using artificial neural networks [J].
Jongepier, AG ;
vanderSluis, L .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) :97-105