Power system frequency response from fixed speed and doubly fed induction generator based wind turbines

被引:199
作者
Holdsworth, L
Ekanayake, JB
Jenkins, N
机构
[1] Univ Manchester, Elect Energy & Power Syst Grp, MCEE, Manchester M60 1QD, Lancs, England
[2] Univ Peradeniya, Dept Elect & Elect Engn, Peradeniya, Sri Lanka
[3] Univ Manchester, Tyndall Ctr Climate Change Res UK, Manchester M60 1QD, Lancs, England
关键词
wind turbines; fixed speed; doubly-fed; inertia; frequency response;
D O I
10.1002/we.105
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Throughout Europe there is an increasing trend of connecting high penetrations of wind turbines to the transmission networks. This has resulted in transmission system operators revising their grid code documents for the connection of large wind forms. These specifications require large MW capacity wind farms to have the ability to assist in some, of the power system control services currently carried out by conventional synchronous generation. These services include voltage and frequency control. It is now recognized that much of this new wind generation plant will use either fixed speed induction generator (FDIG)- or doubly fed induction generator (DFIG)-based wind turbines. The addition of a control loop to synthesize inertia in the DFIG wind turbine using the power electronic control system has been described. The possibility of deloading wind turbines for frequency response using blade pitch angle control is discussed. A pitch control scheme to provide frequency response from FSIG and DFIG wind turbines is also described. A case study of an FSIG wind turbine with frequency response capabilities is investigated. Copyright (C) 2004 John Wiley Sons, Ltd.
引用
收藏
页码:21 / 35
页数:15
相关论文
共 13 条
  • [1] AKMATOV V, 2001, WIND ENG, V25, P367
  • [2] Burton T, 2001, Wind Energy Handbook
  • [3] Control of DFIG wind turbines
    Ekanayake, J
    Holdsworth, L
    Jenkins, N
    [J]. POWER ENGINEER, 2003, 17 (01): : 28 - 32
  • [4] Dynamic modeling of doubly fed induction generator wind turbines
    Ekanayake, JB
    Holdsworth, L
    Wu, XG
    Jenkins, N
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2003, 18 (02) : 803 - 809
  • [5] NGC experience with frequency control in England and Wales - Provision of frequency response by generators
    Erinmez, IA
    Bickers, DO
    Wood, GF
    Hung, WW
    [J]. IEEE POWER ENGINEERING SOCIETY - 1999 WINTER MEETING, VOLS 1 AND 2, 1999, : 590 - 596
  • [6] *GARR HASS PARTN, 2003, BLADED WIND US THEOR
  • [7] Heier S, 2014, Grid integration of wind energy: onshore and offshore conversion systems
  • [8] Comparison of fixed speed and doubly-fed induction wind turbines during power system disturbances
    Holdsworth, L
    Wu, XG
    Ekanayake, JB
    Jenkins, N
    [J]. IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2003, 150 (03) : 343 - 352
  • [9] Kundur P., 1994, POWER SYSTEM STABILI
  • [10] *NAT GRID CO, 2001, 7 YEAR STAT