Hybrid evaporator model: Analysis under uncertainty by means of Monte Carlo method

被引:7
作者
Colorado, Dario [1 ]
Ding, Xudong [2 ]
Alfredo Hernandez, J. [1 ]
Alonso, Beatriz [1 ]
机构
[1] Univ Autonoma Estado Morelos, Ctr Invest Ingn & Ciencias Aplicadas CIICAp, Cuernavaca 62209, Morelos, Mexico
[2] Shandong Jianzhu Univ, Sch Informat & Elect Engn, Jinan 250101, Peoples R China
关键词
Hybrid evaporator model; Error propagation; Standard deviation; Levels of uncertainty; R134a; ERROR PROPAGATION; HVAC SYSTEMS; OPTIMIZATION;
D O I
10.1016/j.applthermaleng.2011.10.055
中图分类号
O414.1 [热力学];
学科分类号
摘要
Error propagation from Monte Carlo method is applied to the heat transfer rate (Q) predicted by a hybrid model. This heat transfer rate permitted us to evaluate an evaporator used in a vapor compression refrigeration system. A hybrid model reported in literature was used in order to obtain error propagation in heat transfer rate prediction. The hybrid model used temperatures, mass flow rates and enthalpies from the evaporator. A correlation for the calculation of relative standard deviation (%RSD) of Q as a function of experimental Q (Q(exp)) and %RSDinstrument was obtained. The effect of each operation variable over standard deviation of the heat transfer rate is presented. Greater efforts in calibration and high-precision equipment in evaporator pressure are recommended in order to obtain meaningful heat transfer rate hybrid prediction with relatively small errors of less than 2.85%. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:148 / 152
页数:5
相关论文
共 18 条
[1]   ERROR PROPAGATION BY MONTE-CARLO METHOD IN GEOCHEMICAL CALCULATIONS [J].
ANDERSON, GM .
GEOCHIMICA ET COSMOCHIMICA ACTA, 1976, 40 (12) :1533-1538
[2]  
[Anonymous], 1999, SPRINGER SCI
[3]  
Bevington P.R., 2003, DATA REDUCTION ERROR
[4]   An elemental NTU-ε model for vapour-compression liquid chillers [J].
Browne, MW ;
Bansal, PK .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2001, 24 (07) :612-627
[5]   Error propagation on COP prediction by artificial neural network in a water purification system integrated to an absorption heat transformer [J].
Colorado, D. ;
Hernandez, J. A. ;
El Hamzaoui, Y. ;
Bassam, A. ;
Siqueiros, J. ;
Andaverde, J. .
RENEWABLE ENERGY, 2011, 36 (05) :1315-1322
[6]   Error Propagation on a Hybrid Evaporator Model [J].
Colorado, Dario ;
Ding, Xudong ;
Hernandez, Jose Alfredo ;
Andaverde, Jorge ;
Juarez, David .
PRES 2011: 14TH INTERNATIONAL CONFERENCE ON PROCESS INTEGRATION, MODELLING AND OPTIMISATION FOR ENERGY SAVING AND POLLUTION REDUCTION, PTS 1 AND 2, 2011, 25 :393-+
[7]   Evaporator modeling - A hybrid approach [J].
Ding, Xudong ;
Cai, Wenjian ;
Jia, Lei ;
Wen, Changyun .
APPLIED ENERGY, 2009, 86 (01) :81-88
[8]   A hybrid condenser model for real-time applications in performance monitoring, control and optimization [J].
Ding, Xudong ;
Cai, Wenjian ;
Jia, Lei ;
Wen, Changyun ;
Zhang, Guiqing .
ENERGY CONVERSION AND MANAGEMENT, 2009, 50 (06) :1513-1521
[9]   A simplified modeling of mechanical cooling tower for control and optimization of HVAC systems [J].
Jin, Guang-Yu ;
Cai, Wen-Jian ;
Lu, Lu ;
Lee, Eng Lock ;
Chiang, Andrew .
ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (02) :355-365
[10]  
Kays W.M., 1984, COMPACT HEAT EXCHANG, V3rd