Optimal placement of phasor measurement units for power system observability

被引:363
作者
Chakrabarti, Saikat
Kyriakides, Elias
机构
[1] University of Cyprus, Nicosia
关键词
benchmarking; exhaustive search; measurement redundancy; observability; optimal placement; phasor measurement units; state estimation;
D O I
10.1109/TPWRS.2008.922621
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a method for optimal placement of phasor measurement units (PMUs) for complete observability of a power system for normal operating conditions, as well as for single branch outages. A binary search algorithm is used to determine the minimum number of PMUs needed to make the system observable. In case of more than one solution, a strategy is proposed to select the solution resulting in the most preferred pattern of measurement redundancy. The proposed method is used to benchmark the optimal PMU placement solutions for the IEEE 14-bus, IEEE 24-bus, IEEE 30-bus and New England 39-bus test systems. The proposed method is applied on a 298-bus system to determine the optimal placement of PMUs when conventional measurements are available.
引用
收藏
页码:1433 / 1440
页数:8
相关论文
共 19 条
[1]  
Abur A., 2004, Power System State Estimation: Theory and Implementation
[2]   POWER-SYSTEM OBSERVABILITY WITH MINIMAL PHASOR MEASUREMENT PLACEMENT [J].
BALDWIN, TL ;
MILI, L ;
BOISEN, MB ;
ADAPA, R .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1993, 8 (02) :707-715
[3]  
*CAN US POW SYST O, 2004, FIN REP AUG 14 2003
[4]  
CHAKRABARTI S, 2007, P IEEE S INT SIGN PR
[5]  
Christie R., 1999, POWER SYSTEM TEST AR
[6]  
ISO-IEC-OIML-BIPM, 1992, GUID EXPR UNC MEAS
[7]  
Mifsud CharlesJ., 1963, COMMUN ACM, V6, P103
[8]   Nondominated sorting genetic algorithm for optimal phasor measurement placement [J].
Milosevic, B ;
Begovic, M .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2003, 18 (01) :69-75
[9]  
Monticelli, 1999, STATE ESTIMATION ELE
[10]  
NOVOSEL D, 2006, PERFORMANCE REQUIR 2