Automated transmission line fault analysis using synchronized sampling at two ends

被引:102
作者
Kezunovic, M [1 ]
Perunicie, B [1 ]
机构
[1] LAMAR UNIV,BEAUMONT,TX 77710
基金
美国国家航空航天局;
关键词
fault analysis; fault detection; fault classification; fault location; synchronized sampling;
D O I
10.1109/59.486131
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper introduces a new approach to fault analysis using synchronized sampling. A digital fault recorder with Global Positioning System (GPS) satellite receiver is the source of data for this approach. Fault analysis functions, such as fault detection, classification and location are implemented for a transmission line using synchronized samples from two ends of a line. This technique can be extremely fast, selective and accurate, providing fault analysis performance that can not easily be matched by other known techniques.