Fault Location for Underground Power Cable Using Distributed Parameter Approach

被引:93
作者
Yang, Xia [1 ]
Choi, Myeon-Song [1 ]
Lee, Seung-Jae [1 ]
Ten, Chee-Wooi [2 ]
Lim, Seong-Il [3 ]
机构
[1] Myongji Univ, Dept Elect Engn, Next Generat Power Technol Ctr, Yongin 449728, South Korea
[2] Iowa State Univ Sci & Technol, Dept Elect & Comp Engn, Ames, IA 50010 USA
[3] Kyungnam Univ, Dept Elect Engn, Masan 631701, South Korea
关键词
Distributed parameter circuit; distribution system; fault location; underground power cable;
D O I
10.1109/TPWRS.2008.2002289
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes an extensive fault location model for underground power cable in distribution system using voltage and current measurements at the sending-end. First, an equivalent circuit that models a faulted underground cable system is analyzed using distributed parameter approach. Then, the analysis of sequence networks in three-phase network is obtained by applying the boundary conditions. This analysis is used to calculate a fault distance in single section using voltage and current equations. The extension to multi-section is further analyzed based on Korean distribution systems. This method is an iterative process to determine a faulted section from the network. Finally, the case studies are evaluated with variations of fault distance and resistance, which also includes the evaluation of its robustness to load uncertainty.
引用
收藏
页码:1809 / 1816
页数:8
相关论文
共 13 条
[1]  
[Anonymous], 2003, ELECT POWER CABLE EN
[2]  
BASCOM EC, 1994, PROCEEDINGS OF THE 1994 IEEE POWER ENGINEERING SOCIETY TRANSMISSION AND DISTRIBUTION CONFERENCE, P376, DOI 10.1109/TDC.1994.328403
[3]   Radio frequency coupling between an antenna and two unshielded parallel wires above a metal sheet - Measurement precautions [J].
Becker, LH ;
Cloete, JH ;
Reader, HC .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2001, 43 (01) :85-88
[4]  
Bungay E., 1990, ELECT CABLE HDB, V2nd
[5]   A new fault location algorithm using direct circuit analysis for distribution systems [J].
Choi, MS ;
Lee, SJ ;
Lee, DS ;
Jin, BG .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :35-41
[6]  
CHOI MS, 2005, KIEE T POWER ENG JUN, P267
[7]  
Clegg B., 1993, Underground Cable Fault Location
[8]  
Kersting W. H., 2001, Distribution System Modeling and Analysis
[9]  
Moshtagh J., 2004, Eighth IEE International Conference on Developments in Power System Protection, P228, DOI 10.1049/cp:20040105
[10]  
Potivejkul S, 2000, 2000 IEEE POWER ENGINEERING SOCIETY WINTER MEETING - VOLS 1-4, CONFERENCE PROCEEDINGS, P724, DOI 10.1109/PESW.2000.850153