Direct lightning strikes to the lightning protective system of a residential building: Triggered-lightning experiments

被引:65
作者
Rakov, VA [1 ]
Uman, MA [1 ]
Fernandez, MI [1 ]
Mata, CT [1 ]
Rambo, KJ [1 ]
Stapleton, MV [1 ]
Sutil, RR [1 ]
机构
[1] Univ Florida, Dept Elect & Comp Engn, Gainesville, FL 32601 USA
基金
美国国家科学基金会;
关键词
ground rods; lightning; lightning protective system; surge protective devices;
D O I
10.1109/61.997942
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Lightning triggered from natural thunderclouds using the rocket-and-wire technique was employed in order to subject to direct lightning strikes the lightning protective system of a test house at the International Center for Lightning Research and Testing (ICLRT) at Camp Blanding, FL. The electrical circuit of the test house was connected to the secondary of a padmount distribution transformer located a distance of about 50 in from the house. The transformer primary was connected to a 650-m long unenergized underground power cable. The test house had two ground rods, one for the lightning protective system grounding and the other for the power supply system grounding. The two rods were about 3 m apart and were connected by a metallic cable. Lightning current was injected into the lightning protective system ground rod, and the currents and voltages at different points in the test system were measured. The waveshapes of currents in the ground rods of the test house differed markedly from the current waveshapes in other parts of the overall system. The ground rods at the test house appeared to filter out the higher frequency components of the lightning current, allowing the lower frequency components of the current to enter the house's electrical circuit, that is, the ground rods appeared to exhibit a capacitive behavior rather than the often expected resistive behavior. This effect was observed for dc grounding resistances of the rods (driven in sandy soil with conductivity of about 2.5 x 10(-4) S/m) ranging from more than a thousand ohms to some tens of ohms. The peak values of 1) the current entering the test house's electrical circuit, 2) the current flowing to the distribution transformer secondary neutral, and 3) the current flowing through the surge protective devices at the test house's service entrance were observed to be greater than in either of the two scenarios suggested by the International Electrotechnical Commission.
引用
收藏
页码:575 / 586
页数:12
相关论文
共 9 条
[1]  
[Anonymous], 1998, PROTECTION STRUCTURE
[2]  
BEJLERI M, 2000, P 25 INT C LIGHTN PR, P825
[3]  
BIRKL J, 1996, P 23 INT C LIGHTN PR, P622
[4]  
FERNANDEZ MI, 1998, TR109670R1 EPRI
[5]  
GRCEV L, 1998, P CIGRE SESS, P36
[6]  
*IEC, 1990, 610241 IEC
[7]   EMTP modeling of a triggered-lightning strike to the phase conductor of an overhead distribution line [J].
Mata, CT ;
Fernandez, MI ;
Rakov, VA ;
Uman, MA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (04) :1175-1181
[8]  
RAKOTOMALA A, 1994, P IEEE INT S EMC, P419
[9]   New insights into lightning processes gained from triggered-lightning experiments in Florida and Alabama [J].
Rakov, VA ;
Uman, MA ;
Rambo, KJ ;
Fernandez, MI ;
Fisher, RJ ;
Schnetzer, GH ;
Thottappillil, R ;
Eybert-Berard, A ;
Berlandis, JP ;
Lalande, P ;
Bonamy, A ;
Laroche, P ;
Bondiou-Clergerie, A .
JOURNAL OF GEOPHYSICAL RESEARCH-ATMOSPHERES, 1998, 103 (D12) :14117-14130