Estimating damping effectiveness of BPA's thyristor controlled series capacitor by applying time and frequency domain methods to measured response

被引:11
作者
Trudnowski, DJ
Donnelly, MK
Hauer, JF
机构
[1] Pacific Northwest Laboratory, Richland
关键词
D O I
10.1109/59.496151
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Recently, a 500-kV thyristor controlled series capacitor (TCSC) was installed in the Bonneville Power Administration system in the northwestern United States, Extensive field testing has-included modulation experiments-to determine the effect of the TCSC on low-frequency oscillations, This paper discusses modulation procedures, analysis methods, and results for estimating the damping effectiveness of the TCSC, Modulation methods include driving the TCSC with step and random noise, and analysis techniques include time (Prony analysis) and frequency-domain identification. Results indicate that: 1) the TCSC can have significant impact on system dynamics; and 2) under a very small feedback gain, the TCSC provides measurable added damping.
引用
收藏
页码:761 / 766
页数:6
相关论文
共 18 条
[1]  
BENDAT JS, 1980, ENG APPLICATIONS COR
[2]   CONTROL OF A DYNAMIC BRAKE TO REDUCE TURBINE-GENERATOR SHAFT TRANSIENT TORQUES [J].
DONNELLY, MK ;
SMITH, JR ;
JOHNSON, RM ;
HAUER, JF ;
BRUSH, RW ;
ADAPA, R .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1993, 8 (01) :67-73
[3]  
DOUGLAS J, 1989, EPRI J JUN, P5
[4]  
HAUER J, 1994, FLEX AC TRANSM SYST
[5]   INITIAL RESULTS IN PRONY ANALYSIS OF POWER-SYSTEM RESPONSE SIGNALS [J].
HAUER, JF ;
DEMEURE, CJ ;
SCHARF, LL .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1990, 5 (01) :80-89
[6]  
HAUER JF, 1989, IEEE S EIGENANALYSIS, P105
[7]  
JOHNSON JM, 1993, P 32 IEEE C DEC CONT, V4, P3510
[8]  
KAMWA I, 1992, IEEE PES SUMM POW M
[9]  
Kundur P, 1994, POWER SYSTEM STABILI, V7
[10]  
Oppenheim AV, 1975, DIGITAL SIGNAL PROCE