Electromechanical Transient Modeling of Modular Multilevel Converter Based Multi-Terminal HVDC Systems

被引:171
作者
Liu, Sheng [1 ]
Xu, Zheng [1 ]
Hua, Wen [2 ]
Tang, Geng [1 ]
Xue, Yinglin [1 ]
机构
[1] Zhejiang Univ, Dept Elect Engn, Hangzhou 310027, Zhejiang, Peoples R China
[2] Zhejiang Elect Power Corp Res Inst, Hangzhou 310014, Zhejiang, Peoples R China
基金
国家高技术研究发展计划(863计划);
关键词
Electromagnetic transient; electromechanical transient; modeling; modular multilevel converter; multi-terminal HVDC (MTDC); simplified model; VSC MTDC MODEL; POWER-FLOW; PERFORMANCE; FREQUENCY; IMPACT; MMC;
D O I
10.1109/TPWRS.2013.2278402
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
080906 [电磁信息功能材料与结构]; 082806 [农业信息与电气工程];
摘要
This paper studies the techniques for modeling modular multilevel converter (MMC) based multi-terminal HVDC (MTDC) systems in the electromechanical transient mode. Firstly, the mathematical model of the MMC and its corresponding equivalent circuit are established, which are similar to those of the two level converters. Then, a power flow calculation method for AC/ DC systems containing MMC-MTDC systems is developed. Two dynamic models for MMC-MTDC systems are developed in the paper. One is the detailed model, taking into account of the AC side circuit, the inner controllers, the modulation strategies, the outer controllers and the MTDC circuit. The other is the simplified model, which only reserves the outer controllers and partial dynamics of the MTDC circuit based on a quantitative analysis of the detailed model's dynamic processes, and it can be used in electromechanical transient simulation with a larger step size. Both the detailed and the simplified models are implemented on PSS/E and compared with the accurate electromagnetic transient models on PSCAD in a four terminal MMC-MTDC system; the result proves the validity of the developed models. Lastly, a stability study of a modified New England 39-bus system is executed, and the result shows that the AC fault can be isolated well in an MMC-MTDC asynchronously connected AC grid.
引用
收藏
页码:72 / 83
页数:12
相关论文
共 29 条
[1]
[Anonymous], 2008, CIGRE SESS PAR FRANC
[2]
[Anonymous], P 13 EUR C POW EL AP
[3]
[Anonymous], 2003, Power system electromagnetic transients simulation
[4]
[Anonymous], CIGRE SC B4 2009 BER
[5]
[Anonymous], P 2010 INT POW EL C
[6]
[Anonymous], CIGRE S OS JAP
[7]
Modeling and control of Multi-terminal VSC HVDC systems [J].
Beerten, Jef ;
Belmans, Ronnie .
SELECTED PAPERS FROM DEEP SEA OFFSHORE WIND R&D CONFERENCE, 2012, 24 :123-130
[8]
Generalized Steady-State VSC MTDC Model for Sequential AC/DC Power Flow Algorithms [J].
Beerten, Jef ;
Cole, Stijn ;
Belmans, Ronnie .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2012, 27 (02) :821-829
[9]
Bergeron L., 1961, WATER HAMMER HYDRAUL
[10]
Adaptive Droop Control for Effective Power Sharing in Multi-Terminal DC (MTDC) Grids [J].
Chaudhuri, Nilanjan Ray ;
Chaudhuri, Balarko .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (01) :21-29