Determination of load shedding for power-flow solvability using outage-continuation power flow (OCPF)

被引:10
作者
Song, H. [1 ]
Baik, S. -D.
Lee, B.
机构
[1] Kunsan Natl Univ, Sch Elect & Informat Engn, Kunsan 573701, Joenbuk, South Korea
[2] Korea Univ, Dept Elect Engn, Seoul 136701, South Korea
[3] Korea Elect Power Corp, Suwon Power Transmiss Ctr, Suwon, South Korea
关键词
D O I
10.1049/ip-gtd:20045200
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper proposes a methodology that determines control strategies of load shedding for restoring power-flow solvability in unsolvable cases using a new tool of outage-continuation power flow (OCPF). A specified outage from a set of multiple contingencies is modelled with a homotopy function, including a parameter representing the outage. The new tool traces the path of solutions satisfying the power-flow equations with respect to variations of the parameter. At the nose point, it performs a sensitivity analysis with a normal vector to identify the most effective control variables. With the sensitivity information, location of load shedding is determined; then, an adequate amount of control is decided by applying a searching method. In numerical simulation, an illustrative example of the proposed framework is shown applied to the New England 39-bus system.
引用
收藏
页码:321 / 325
页数:5
相关论文
共 11 条
[1]   THE CONTINUATION POWER FLOW - A TOOL FOR STEADY-STATE VOLTAGE STABILITY ANALYSIS [J].
AJJARAPU, V ;
CHRISTY, C .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (01) :416-423
[2]   COMPUTING AN OPTIMUM DIRECTION IN CONTROL SPACE TO AVOID SADDLE NODE BIFURCATION AND VOLTAGE COLLAPSE IN ELECTRIC-POWER SYSTEMS [J].
DOBSON, I ;
LU, LM .
IEEE TRANSACTIONS ON AUTOMATIC CONTROL, 1992, 37 (10) :1616-1620
[3]   NEW METHODS FOR COMPUTING A CLOSEST SADDLE NODE BIFURCATION AND WORST-CASE LOAD POWER MARGIN FOR VOLTAGE COLLAPSE [J].
DOBSON, I ;
LU, LM .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1993, 8 (03) :905-913
[4]   Practical minimum load shedding strategy to mitigate voltage collapse [J].
Feng, ZH ;
Ajjarapu, V ;
Maratukulam, DJ .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1998, 13 (04) :1285-1291
[5]   A new continuation power flow tool for investigating the nonlinear effects of transmission branch parameter variations [J].
Flueck, AJ ;
Dondeti, JR .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2000, 15 (01) :223-227
[6]   Application of interior point methods to power flow unsolvability [J].
Granville, S ;
Mello, JCO ;
Melo, ACG .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (02) :1096-1103
[7]   Invariant subspace parametric sensitivity (ISPS) of structure-preserving power system models [J].
Lee, BJ ;
Ajjarapu, V .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (02) :845-850
[8]   COMPUTATION OF A PRACTICAL METHOD TO RESTORE POWER-FLOW SOLVABILITY [J].
OVERBYE, TJ .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (01) :280-287
[9]   A POWER-FLOW MEASURE FOR UNSOLVABLE CASES [J].
OVERBYE, TJ .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1994, 9 (03) :1359-1365
[10]   Reactive reserve-based contingency constrained optimal power flow (RCCOPF) for enhancement of voltage stability margins [J].
Song, HC ;
Lee, BJ ;
Kwon, SH ;
Ajjarapu, V .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2003, 18 (04) :1538-1546