Network voltage controller for distributed generation

被引:64
作者
Hird, CM
Leite, H
Jenkins, N
Li, H
机构
[1] Econnect Ltd, Hexham NE46 3PU, Northd, England
[2] UMIST, Dept Elect Engn & Elect, Manchester M60 1QD, Lancs, England
关键词
D O I
10.1049/ip-gtd:20040083
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Present distribution network voltage design practice limits the distributed generation capacity that can be connected to 11 kV networks. It has been shown previously that adoption of a more active approach to network voltage control can significantly increase distributed generation capacity. One way to do this is to control the target voltage of automatic voltage control relays at primary substations. A basic design for a controller to do this has been created, comprising three algorithms. A statistical state estimation algorithm estimates the voltage magnitude at each network node supplied by the primary substation, using real-time measurements, network data and load data. The estimate accuracy depends on the number and placement of real-time measurements. Studies using an 11 kV feeder model showed that an acceptable accuracy could be obtained with one or two measurements. The state estimator uses pseudo measurements for unmeasured loads. A load model was constructed using load profiles to calculate the pseudo measurements. The calculated pseudo measurements were inaccurate, but it was found that acceptable state estimate accuracy could be obtained with inaccurate pseudo measurements. A control algorithm alters the AVC relay target voltage, based on the maximum and minimum node voltage magnitude estimates. A simulation on a four-feeder network showed that the algorithm enabled the generator power export to be more than doubled.
引用
收藏
页码:150 / 156
页数:7
相关论文
共 12 条
[1]  
ALLERA SV, 1998, DISTR EUR DA DSM C L
[2]   STATE ESTIMATION FOR REAL-TIME MONITORING OF DISTRIBUTION-SYSTEMS [J].
BARAN, ME ;
KELLEY, AW .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1994, 9 (03) :1601-1609
[3]   MODELING AND ANALYSIS OF UNDER-LOAD TAP-CHANGING TRANSFORMER CONTROL-SYSTEMS [J].
CALOVIC, MS .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (07) :1909-1915
[4]   Load modeling for distribution circuit state estimation [J].
Ghosh, AK ;
Lubkeman, DL ;
Jones, RH .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (02) :999-1005
[5]   BAD DATA-ANALYSIS FOR POWER-SYSTEM STATE ESTIMATION [J].
HANDSCHIN, E ;
SCHWEPPE, FC ;
KOHLAS, J ;
FIECHTER, A .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1975, PA94 (02) :329-337
[6]   State estimation for power distribution system and measurement impacts [J].
Li, K .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (02) :911-916
[7]   Maximising penetration of wind generation in existing distribution networks [J].
Liew, SN ;
Strbac, G .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2002, 149 (03) :256-262
[8]   DISTRIBUTION-SYSTEM STATE ESTIMATION [J].
LU, CN ;
TENG, JH ;
LIU, WHE .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (01) :229-240
[9]  
Monticelli, 1999, STATE ESTIMATION ELE
[10]  
*VA TECH REYROLLE, 2000, TECHN MAN SUP MICR V