Adaptive non-communication protection for power lines BO scheme 1 - The delayed operation approach

被引:34
作者
Bo, ZQQ [1 ]
机构
[1] ALSTOM T&D Protect & Control Ltd, Stafford ST17 4LX, England
关键词
adaptive protection; BO protection; non-communication protection;
D O I
10.1109/61.974192
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 [电气工程]; 0809 [电子科学与技术];
摘要
This paper proposes a new technique in power line protection, the "adaptive non-communication protection." In this technique, protection relays make operate or restraint decisions, adapting to system and fault conditions, without the need for communication links. Operation without communication links to signal the remote end relay is achieved by the detection and identification of the operation of the circuit breaker at remote end of the protected line section. An algorithm based on the symmetric components is proposed to detect and identify the balance condition of the system during the fault. The paper is focused on one of the three protection schemes based on the new technique, the delayed operation scheme.. Simulation studies carried out for various systems and fault conditions have demonstrated the feasibility of the scheme.
引用
收藏
页码:85 / 91
页数:7
相关论文
共 8 条
[1]
A new non-communication protection technique for transmission lines [J].
Bo, ZQ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (04) :1073-1078
[2]
BO ZQ, 2002, IEEE T POWER DEL JAN, P97
[3]
BO ZQ, 2002, IEEE T POWER DEL JAN, P92
[4]
BO ZQ, 1997, P IEE INT C DEV POW, P291
[5]
ELMORE W, 1989, P 43 ANN GEORG PROT
[6]
ADAPTIVE TRANSMISSION-SYSTEM RELAYING [J].
HOROWITZ, SH ;
PHADKE, AG ;
THORP, JS .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) :1436-1445
[7]
NONUNIT PROTECTION TECHNIQUE FOR EHV TRANSMISSION-SYSTEMS BASED ON FAULT-GENERATED NOISE .1. SIGNAL MEASUREMENT [J].
JOHNS, AT ;
AGGARWAL, RK ;
BO, ZQ .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1994, 141 (02) :133-140
[8]
ADAPTIVE TRANSMISSION RELAYING CONCEPTS FOR IMPROVED PERFORMANCE [J].
ROCKEFELLER, GD ;
WAGNER, CL ;
LINDERS, JR ;
HICKS, KL ;
RIZY, DT .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) :1446-1458