Lighting and energy performance for an office using high frequency dimming controls

被引:110
作者
Li, DHW [1 ]
Lam, TNT [1 ]
Wong, SL [1 ]
机构
[1] City Univ Hong Kong, Dept Bldg & Construct, Bldg Energy Res Grp, Kowloon, Hong Kong, Peoples R China
关键词
daylight availability; energy savings; frequency distribution; high frequency dimming controls; on-off controls;
D O I
10.1016/j.enconman.2005.06.016
中图分类号
O414.1 [热力学];
学科分类号
摘要
Artificial lighting is one of the major electricity consuming items in many non-domestic buildings. Recently, there has been an increasing interest in incorporating daylight in architectural and building designs to reduce the electricity use and enhance greener building developments. This paper presents field measurements for a fully air conditioned open plan office using a photoelectric dimming system. Electric lighting load, indoor illuminance levels and daylight availability were systematically measured and analyzed. The general features and characteristics of the results such as electric lighting energy savings and transmitted daylight illuminance in the forms of frequency distributions and cumulative frequency distributions are presented. Daylighting theories and regression models have been developed and discussed. It has been found that energy savings in electric lighting were over 30% using the high frequency dimming controls. The results from the study would be useful and applicable to other office spaces with similar architectural layouts and daylight linked lighting control systems. (c) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1133 / 1145
页数:13
相关论文
共 19 条
[1]
Energy performance of daylight-linked automatic lighting control systems in large atrium spaces: report on two field-monitored case studies [J].
Atif, MR ;
Galasiu, AD .
ENERGY AND BUILDINGS, 2003, 35 (05) :441-461
[2]
Global energy savings in offices buildings by the use of daylighting [J].
Bodart, M ;
De Herde, A .
ENERGY AND BUILDINGS, 2002, 34 (05) :421-429
[3]
The characteristics of photosensors and electronic dimming ballasts in daylight responsive dimming systems [J].
Choi, AS ;
Song, KD ;
Kim, YS .
BUILDING AND ENVIRONMENT, 2005, 40 (01) :39-50
[4]
CIBSE, 1987, CHART I BUILD SERV E
[5]
An analysis of electricity end-use in air-conditioned office buildings in Hong Kong [J].
Lam, JC ;
Li, DHW ;
Cheung, SO .
BUILDING AND ENVIRONMENT, 2003, 38 (03) :493-498
[6]
An investigation of daylighting performance and energy saving in a daylit corridor [J].
Li, DHW ;
Lam, JC .
ENERGY AND BUILDINGS, 2003, 35 (04) :365-373
[7]
An analysis of lighting energy savings and switching frequency for a daylit corridor under various indoor design illuminance levels [J].
Li, DHW ;
Lam, JC .
APPLIED ENERGY, 2003, 76 (04) :363-378
[8]
Evaluation of lighting performance in office buildings with daylighting controls [J].
Li, DHW ;
Lam, JC .
ENERGY AND BUILDINGS, 2001, 33 (08) :793-803
[9]
Li DHW, 2002, ARCHITECTURAL SCI RE, V45, P21
[10]
Littlefair P. J., 2001, Lighting Research and Technology, V33, P43, DOI 10.1177/136578280103300108