A coupled numerical approach on museum air conditioning: Energy and fluid-dynamic analysis

被引:47
作者
Ascione, Fabrizio [1 ]
Bellia, Laura [2 ]
Capozzoli, Alfonso [3 ]
机构
[1] Univ Sannio, DING, I-82100 Benevento, Italy
[2] Univ Naples Federico II, DETEC, I-80125 Naples, Italy
[3] Politecn Torino, DENERG, TEBE Res Grp, I-10129 Turin, Italy
关键词
Museums; HVAC systems; BEPS; Energy saving; CFD; Air diffusers; BUILDING ENERGY;
D O I
10.1016/j.apenergy.2012.10.007
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In the museum environment, the temporal stability and the spatial uniformity of the indoor microclimatic parameters are necessary primarily for the correct artwork conservation and then for the occupant thermal comfort. Therefore, a HVAC system is usually necessary. This paper above all emphasizes the integration of Building Energy Performance Simulation (BEPS) and Computational Fluid Dynamics (CFD) codes. This coupled numerical approach can provide accurate information about both the HVAC system energy request and the indoor microclimatic control (temporal and spatial distribution of the parameters). Then, a case study concerning a typical museum exhibition room is examined. The annual energy request for three types of all-air system, as well as the temporal variation of indoor temperature and relative humidity, is evaluated by means of a BEPS code. Energy savings can be obtained using a system with desiccant wheel (11%) or enthalpy wheel (9%), compared to the base system. As regards indoor relative humidity control, this is more critical for summer conditions, and the best performance is obtained by the system with desiccant wheel. Then, the spatial microclimatic control is analyzed by means of a CFD analysis, for various thermal load conditions and different air diffusion xequipments. The best performances are obtained by using the swirling (vortex) diffusers; also the perimetrical stripes of slot diffusers show satisfactory performances. Finally, in order to evaluate the ability of air diffusion equipments to assure good ventilation effectiveness, an analysis of the mean age of air is carried out too. (c) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:416 / 427
页数:12
相关论文
共 45 条
[1]   A case study for influence of building thermal insulation on cooling load and air-conditioning system in the hot and humid regions [J].
Aktacir, Mehmet Azmi ;
Buyukalaca, Orhan ;
Yilmaz, Tuncay .
APPLIED ENERGY, 2010, 87 (02) :599-607
[2]  
[Anonymous], 2006, US GUID
[3]  
[Anonymous], ASHRAE HDB FUND
[4]  
Ascione F, 2006, 5 INT C SUST EN TECH
[5]   Earth-to-air heat exchangers for Italian climates [J].
Ascione, Fabrizio ;
Bellia, Laura ;
Minichiello, Francesco .
RENEWABLE ENERGY, 2011, 36 (08) :2177-2188
[6]   Microclimatic control in the museum environment: Air diffusion performance [J].
Ascione, Fabrizio ;
Minichiello, Francesco .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (04) :806-814
[7]   Solar gain and building envelope: the surface factor [J].
Ascione, Fabrizio ;
Bellia, Laura ;
Mazzei, Pietro ;
Minichiello, Francesco .
BUILDING RESEARCH AND INFORMATION, 2010, 38 (02) :187-205
[8]   Energy saving strategies in air-conditioning for museums [J].
Ascione, Fabrizio ;
Bellia, Laura ;
Capozzoli, Alfonso ;
Minichiello, Francesco .
APPLIED THERMAL ENGINEERING, 2009, 29 (04) :676-686
[9]  
ASHRAE, 1991, 701991 ANSIASHRAE
[10]  
ASHRAE, 2007, ASHRAE HDB HVAC APPL