Use of the WECC WAMS in Wide-Area Probing Tests for Validation of System Performance and Modeling

被引:76
作者
Hauer, John F. [1 ]
Mittelstadt, William A. [2 ]
Martin, Kenneth E. [2 ]
Burns, James W. [2 ]
Lee, Harry [3 ]
Pierre, John W. [4 ]
Trudnowski, Daniel J. [5 ]
机构
[1] Pacific NW Natl Lab, Richland, WA 99352 USA
[2] Bonneville Power Adm, Vancouver, WA 98662 USA
[3] British Columbia Hudro, Burnaby, BC V3N 4X8, Canada
[4] Univ Wyoming, Laramie, WY 82071 USA
[5] Univ Montana, Montana Tech, Butte, MT 59701 USA
关键词
Performance monitoring; phasor measurements; system testing; Wide-Area Measurement System (WAMS); ELECTROMECHANICAL MODES; IDENTIFICATION;
D O I
10.1109/TPWRS.2008.2009429
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
During 2005 and 2006, the Western Electricity Coordinating Council (WECC) performed three major tests of western system dynamics. These tests used a Wide-Area Measurement System (WAMS) based primarily on phasor measurement units (PMUs) to determine response to events including the insertion of the 1400-MW Chief Joseph braking resistor, probing signals, and ambient events. Test security was reinforced through real-time analysis of wide-area effects, and high-quality data provided dynamic profiles for interarea modes across the entire western interconnection. The tests established that low-level optimized pseudo-random +/- 20-MW probing with the Pacific DC Intertie (PDCI) roughly doubles the apparent noise that is natural to the power system, providing sharp dynamic information with negligible interference to system operations. Such probing is an effective alternative to use of the 1400-MW Chief Joseph dynamic brake, and it is under consideration as a standard means for assessing dynamic security.
引用
收藏
页码:250 / 257
页数:8
相关论文
共 15 条
[1]   Bootstrap-based confidence interval estimates for electromechanical modes from multiple output analysis of measured ambient data [J].
Anderson, MG ;
Zhou, N ;
Pierre, JW ;
Wies, RW .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2005, 20 (02) :943-950
[2]  
Atanackovic D, 2008, IEEE POWER ENERGY M, V6, P61, DOI [10.1109/MPAE.2008.4412941, 10.1109/MPE.2007.910026]
[3]  
*EPRI, 1999, TR112031 EPRI
[4]   SQUARE BUTTE HVDC MODULATION SYSTEM FIELD-TESTS [J].
GRUND, CE ;
HAUER, JF ;
CRANE, LP ;
CARLSON, DL ;
WRIGHT, SE .
IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (01) :351-357
[5]  
Hauer J, 1999, TR112031 EPRI
[6]   POWER SYSTEM IDENTIFICATION BY FITTING STRUCTURED MODELS TO MEASURED FREQUENCY-RESPONSE [J].
HAUER, JF .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (04) :915-923
[7]  
HAUER JF, 2000, INTERIM REPORT MODEL
[8]  
HAUER JF, 1987, IEEE PUBLICATION, P79
[9]  
HAUER JF, 2007, INTEGRATED DYNAMIC I, pCH14
[10]  
HAUER JF, 2007, INTERIM REPORT WECC