Experimental studies on the characteristics of an absorber using LiBr/H2O solution as working fluid

被引:72
作者
Deng, SM [1 ]
Ma, WB [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Peoples R China
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 1999年 / 22卷 / 04期
关键词
absorber; falling film; absorption; water lithium bromide;
D O I
10.1016/S0140-7007(98)00067-X
中图分类号
O414.1 [热力学];
学科分类号
摘要
The absorber is an important component in absorption machines and its characteristics have significant effect on the overall efficiency of absorption machines. This article reports on the results of experimental studies on the characteristics for a falling film absorber which is made up of 24 row horizontal smooth tubes. It shows that while the mass transfer coefficient is increased with the increase of spray density, the heat transfer coefficient is increased only in small spray density range. There is an optimum spray density between 0.005 and 0.055 kg s(-1) m(-1) spray density at which the heat transfer coefficient is maximum. The heat transfer coefficient (Nusselt number), which is traditionally expressed using Reynolds number and Prandtl number, was modified taking the effect of inlet solution concentration into account. The results can be used to optimize the future design of absorption machines having a falling film absorber and using LiBr/H2O as working fluid. (C) 1999 Elsevier Science Ltd and IIR. All rights reserved.
引用
收藏
页码:293 / 301
页数:9
相关论文
共 10 条
[1]  
Andberg J.W., 1987, ASHRAE T, V93, P2454
[2]  
CHOUDHURY SK, 1993, ASHRAE TRAN, V99, P81
[3]  
DAI Y, 1980, LITHIUM BROMIDE ABSO
[4]   SIMULTANEOUS HEAT AND MASS-TRANSFER IN ABSORPTION OF GASES IN TURBULENT LIQUID-FILMS [J].
GROSSMAN, G ;
HEATH, MT .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1984, 27 (12) :2365-2376
[5]  
GROSSMAN G, 1982, P AICHE WINT ANN M O
[6]   ABSORPTION OF WATER-VAPOR INTO FALLING FILMS OF AQUEOUS LITHIUM BROMIDE [J].
KIM, KJ ;
BERMAN, NS ;
CHAU, DSC ;
WOOD, BD .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1995, 18 (07) :486-494
[7]   Theoretical analysis of low-temperature hot source driven two-stage LiBr/H2O absorption refrigeration system [J].
Ma, WB ;
Deng, SM .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1996, 19 (02) :141-146
[8]  
MA WB, 1996, P INT ABS HEAT PUMP, V2, P679
[9]  
PATNAIK V, 1993, ASHRAE TRAN, V99, P69
[10]  
1977, LITHIUM BROMIDE AQUE