System stability of large wind power networks: A Danish study case

被引:25
作者
Akhmatov, V [1 ]
机构
[1] Energinet DK, Transmiss Syst Operator Denmark, DK-7000 Fredericia, Denmark
关键词
wind turbine; short-circuit fault; voltage stability; power loss; power reserves; over-voltage; reactive compensation; power grid; model; simulation;
D O I
10.1016/j.ijepes.2005.10.001
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The article describes the considerations and the results of the investigation on short-term voltage stability carried out on a large wind power network model that is similar to a part of the Danish power grid. In the investigated power network, around 50% of the electricity consumption is covered by wind turbines and local combined heat and power (CHP) units. A distinction is made between local wind turbines that may trip and those in a large wind farm subject to the Grid Specifications of the transmission system operator (TSO) that must ride through the grid faults. When a short-circuit fault occurs in the transmission network, the main concerns are: (i) a risk of uncontrollable voltage sags that may result in voltage instability, (ii) a risk of significant power loss due to tripping of local units and possibly (iii) a risk of over-voltage at the periphery of the transmission network. Significant presence of induction generator based wind turbines is the main reason of a risk of voltage instability manifesting itself by temporarily uncontrollable voltage decay in a part of the power grid and being caused by significant reactive power absorption of the induction generators. However, voltage instability does not necessarily develop to voltage collapse, because local wind turbines will trip at abnormal grid operation, for example, at registering excessive under-voltage. This 'eliminates' the problem of reactive power absorption in the power grid and leads to the voltage reestablishment. However, protective disconnection introduces the new issues such as (i) establishing power reserves and (ii) protecting the periphery of the transmission network from excessive over-voltage. (C) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:48 / 57
页数:10
相关论文
共 17 条
[1]  
Akhmatov V., 2000, Proceedings of the IASTED International Conference Power and Energy Systems, P235
[2]   Modelling and transient stability of large wind farms [J].
Akhmatov, V ;
Knudsen, H ;
Nielsen, AH ;
Pedersen, JK ;
Poulsen, NK .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2003, 25 (02) :123-144
[3]  
AKHMATOV V, 2001, P EUR WIND EN C EWEC
[4]  
AKHMATOV V, IN PRESS INDUCTION G
[5]  
BRUNTT M, 1999, P INT IEEE POW TECHN
[6]  
*DEAN, 2005, INT NAT GRID ONSH OF
[7]  
*DEFU, 1991, KR88 DEFU
[8]  
*DEFU, 1998, KR111E DEFU
[9]  
Eltra, 2000, ELT1999411A ELTR TRA
[10]  
HODSWORTH L, 2004, WIND ENG, V28, P399