A DSP controlled resonant active filter for power conditioning in three-phase industrial power systems

被引:13
作者
Ünsal, A
von Jouanne, AR [1 ]
Stonick, VL
机构
[1] Oregon State Univ, Dept Elect & Comp Engn, Corvallis, OR 97331 USA
[2] Dumlupinar Univ, Dept Elect & Elect Engn, Kutahya, Turkey
关键词
harmonics; active filters; DSP; power quality;
D O I
10.1016/S0165-1684(02)00335-3
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a DSP controlled resonant active filter for power conditioning in three-phase industrial or commercial power systems. The active filter is designed to cancel lower-order harmonics generated by nonlinear loads using a series resonant LC tank tuned to a high frequency along with a pulse-width modulated (PWM) rectifier topology. The PWM control of the active filter allows for independent control of lower-order harmonics to efficiently cancel load-generated harmonics for power quality improvement. The active filter control algorithm is simulated in MATLAB and the real-time harmonic cancellation process is implemented on a DSP and verified through experimental results. (C) 2002 Elsevier Science B.V. All rights reserved.
引用
收藏
页码:1743 / 1752
页数:10
相关论文
共 16 条
[1]   New trends in active filters for power conditioning [J].
Akagi, H .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1996, 32 (06) :1312-1322
[2]  
[Anonymous], IEEE SPECTRUM
[3]  
BOYD M, 1995, POWER QUALITY AS JAN, P56
[4]  
CLEMMENSEN JM, 1993, IEEE SPECTRUM, V30, P40
[5]  
ENJETI P, 1991, PESC 91 RECORD, P382, DOI 10.1109/PESC.1991.162703
[6]   HIGH-POWER ELECTRONICS [J].
HINGORANI, NG ;
STAHLKOPF, KE .
SCIENTIFIC AMERICAN, 1993, 269 (05) :78-85
[7]  
IEEE, 1992, 519 IEEE
[8]   Power interruption costs to industrial and commercial consumers of electricity [J].
Sullivan, MJ ;
Vardell, T ;
Johnson, M .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (06) :1448-1458
[9]  
*TEX INSTR, 1997, SPRA371 TEX INSTR
[10]  
UNSAL A, 1999, ICASSP99 C MARCH