Impedance-Phased Dynamic Control Method for Grid-Connected Inverters in a Weak Grid

被引:328
作者
Chen, Xin [1 ]
Zhang, Yang [1 ]
Wang, Shanshan [1 ]
Chen, Jie [1 ]
Gong, Chunying [1 ]
机构
[1] Nanjing Univ Aeronaut & Astronaut, Coll Automat Engn, Jiangsu Key Lab New Energy Generat & Power Conver, Nanjing 210016, Jiangsu, Peoples R China
基金
国家高技术研究发展计划(863计划);
关键词
Grid-connected inverter; impedance-phased compensation; impedance-phased dynamic control; stability; weak grid; LCL-FILTER; ADAPTIVE-CONTROL; CONVERTERS; STABILITY;
D O I
10.1109/TPEL.2016.2533563
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
080906 [电磁信息功能材料与结构]; 082806 [农业信息与电气工程];
摘要
A power distribution grid exhibits the characteristics of a weak grid owing to the existence of scattered high-power distributed power-generation devices. The grid impedance affects the robust stability of grid-connected inverters, leading to harmonic resonance, or even instability in the system. Therefore, a study of the stability of grid-connected inverters with high grid impedance based on impedance analysis is presented in this paper. The output impedance modeling of an LCL-type single-phase grid-connected inverter is derived, where the effects of the PLL loop and the digital control delays on the output impedance characteristics have been taken into account. To enhance the stability of grid-connected inverters with different grid impedance, a novel impedance-phased compensation control strategy is proposed by increasing the phase margin of the grid-connected inverters. Specifically, a detailed implementation and parameter design of the impedance-phased compensation control method is depicted. Finally, an impedance-phased dynamic control scheme combined with online grid impedance measurement is introduced and also verified by the experiment results.
引用
收藏
页码:274 / 283
页数:10
相关论文
共 25 条
[1]
Suppression of line voltage related distortion in current controlled grid connected inverters [J].
Abeyasekera, T ;
Johnson, CM ;
Atkinson, DJ ;
Armstrong, M .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2005, 20 (06) :1393-1401
[2]
Active Mitigation of Subsynchronous Interactions Between PWM Voltage-Source Converters and Power Networks [J].
Alawasa, Khaled Mohammad ;
Mohamed, Yasser Abdel-Rady Ibrahim ;
Xu, Wilsun .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (01) :121-134
[3]
[Anonymous], 1997, IEEE Standard 1204-1997
[4]
[Anonymous], 2011, QGDW6172011
[5]
[Anonymous], 2003, 15472003 IEEE
[6]
[Anonymous], FOOD ANAL METHODS
[7]
Adaptive Control of Grid-Connected Inverters Based on Online Grid Impedance Measurements [J].
Cespedes, Mauricio ;
Sun, Jian .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2014, 5 (02) :516-523
[8]
Impedance Modeling and Analysis of Grid-Connected Voltage-Source Converters [J].
Cespedes, Mauricio ;
Sun, Jian .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (03) :1254-1261
[9]
Céspedes M, 2012, IEEE ENER CONV, P914, DOI 10.1109/ECCE.2012.6342721
[10]
Ding GQ, 2014, APPL POWER ELECT CO, P2132, DOI 10.1109/APEC.2014.6803601