An iterative two-terminal fault-location method based on unsynchronized phasors

被引:55
作者
Dalcastagne, Andre Luis [1 ]
Noceti Filho, Sidnei [1 ]
Zuern, Hans Helmut [2 ]
Seara, Rui [1 ]
机构
[1] Univ Fed Santa Catarina, LINSE, Circuits & Signal Proc Lab, Dept Elect Engn, BR-88040900 Florianopolis, SC, Brazil
[2] Univ Fed Santa Catarina, LABSPOT, Power Syst Lab, Dept Elect Engn, BR-88040900 Florianopolis, SC, Brazil
关键词
fault location; iterative methods; transmission lines;
D O I
10.1109/TPWRD.2008.2002858
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 [电气工程]; 0809 [电子科学与技术];
摘要
This paper presents a two-terminal fault-location method which works with unsynchronized phasors. The algorithm is iterative and takes a distributed line model into account. At each iteration, the voltage magnitudes computed from the voltage and current phasors measured at the sending and receiving ends are approximated by two straight lines, and the fault-location estimate is obtained by the intersection point of these two lines. The process ends when the difference between two successive fault-location estimates reaches a threshold stipulated by the user. Since the search process is based on voltage magnitudes, the proposed approach does not require synchronism between the measurements obtained at each transmission-line terminal. The evaluation tests show that the fault-location error of the proposed approach is negligible if the phasors measured at both line ends and the line parameters are accurate. For actual fault conditions, the fault-location error is dependent on the accuracy of the phasor magnitudes and transmission-line parameters.
引用
收藏
页码:2318 / 2329
页数:12
相关论文
共 16 条
[1]
BALCEREK P, 2003, IEEE BOL POWERTECH C
[2]
Born E., 1967, Electr. World, V168, P133
[3]
DALCASTAGNE AL, 2006, P INT C POW SYST TEC, P1
[4]
AN ACCURATE FAULT LOCATOR WITH COMPENSATION FOR APPARENT REACTANCE IN THE FAULT RESISTANCE RESULTING FROM REMOTE-END INFEED [J].
ERIKSSON, L ;
SAHA, MM ;
ROCKEFELLER, GD .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1985, 104 (02) :424-436
[5]
A NEW FAULT LOCATION TECHNIQUE FOR 2-TERMINAL AND 3-TERMINAL LINES [J].
GIRGIS, AA ;
HART, DG ;
PETERSON, WL .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (01) :98-107
[6]
*IEEE, 2005, IEEE GUID DET FAULT
[7]
Jiang JA, 2000, IEEE T POWER DELIVER, V15, P1136
[8]
ACCURATE FAULT LOCATION TECHNIQUE FOR POWER TRANSMISSION-LINES [J].
JOHNS, AT ;
JAMALI, S .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1990, 137 (06) :395-402
[9]
DEVELOPMENT OF AN ADVANCED TRANSMISSION-LINE FAULT LOCATION SYSTEM .2. ALGORITHM DEVELOPMENT AND SIMULATION [J].
LAWRENCE, DJ ;
CABEZA, LZ ;
HOCHBERG, LT .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (04) :1972-1983
[10]
Unsynchronized two-terminal fault location estimation [J].
Novosel, D ;
Hart, DG ;
Udren, E ;
Garitty, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (01) :130-138