Calculation of a Health Index for Oil-Immersed Transformers Rated Under 69 kV Using Fuzzy Logic

被引:127
作者
Abu-Elanien, Ahmed E. B. [1 ]
Salama, M. M. A. [1 ,2 ]
Ibrahim, M. [1 ]
机构
[1] Univ Waterloo, Dept Elect & Comp Engn, Waterloo, ON N2L 3G1, Canada
[2] King Saud Univ, Riyadh 11451, Saudi Arabia
关键词
Asset management; condition monitoring; fuzzy logic; health index; transformer end of life; transformer health; POWER TRANSFORMERS; INSULATION;
D O I
10.1109/TPWRD.2012.2205165
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a new method for calculating a health index for transformers (for operating voltage 69 kV or less) based on diagnostic tests. The method relies on the use of furan analysis, dissolved gas analysis, and other oil analysis results as a means of calculating the health index using fuzzy set theory. Real field data for 90 working transformers were used to test the proposed method. The results were compared with the results calculated for the same set of transformers by an experienced asset management and health assessment consulting company. The comparison shows that the results are highly reliable.
引用
收藏
页码:2029 / 2036
页数:8
相关论文
共 30 条
[1]   Asset management techniques for transformers [J].
Abu-Elanien, Ahmed E. B. ;
Salama, M. M. A. .
ELECTRIC POWER SYSTEMS RESEARCH, 2010, 80 (04) :456-464
[2]  
[Anonymous], 2006, IEEE STD C57106 2006, P1, DOI DOI 10.1109/IEEESTD.2006.99501
[3]  
[Anonymous], IEEE T POWER DEL
[4]  
[Anonymous], 20 INT C EL DISTR PR
[5]  
[Anonymous], P PROGN HLTH MAN C J
[6]  
[Anonymous], 2008, TRANS DISTRIB CONF
[7]  
[Anonymous], 17 INT C EL DISTR BA
[8]  
[Anonymous], 2009, IEEE STD C57104 2008, pC1, DOI DOI 10.1109/IEEESTD.2009.4776518
[9]  
[Anonymous], IEEE 11 INT C TRANSM
[10]  
[Anonymous], 18 INT C EXH EL DIST