Experimental investigation of activated carbon fibers/ethanol pairs for adsorption cooling system application

被引:110
作者
El-Sharkawy, II
Kuwahara, K
Saha, BB
Koyama, S
Ng, KC
机构
[1] Kyushu Univ, Inst Mat Chem & Engn, Kasuga, Fukuoka 8168580, Japan
[2] Kyushu Univ, Dept Energy & Environm Engn, Kasuga, Fukuoka 8168580, Japan
[3] Natl Univ Singapore, Dept Mech Engn, Singapore 119260, Singapore
关键词
activated carbon fiber; adsorption characteristics; cooling system; ethanol;
D O I
10.1016/j.applthermaleng.2005.10.010
中图分类号
O414.1 [热力学];
学科分类号
摘要
The objective of this article is to improve the performance of thermally powered adsorption/cooling systems by selecting a new adsorbent/refrigerant pair. Adsorption equilibrium data of ethanol onto Unitika activated carbon fiber (ACF) of types (A-20) and (A-15) have been measured and Dubinin-Radushkevich (D-R) equation is used to fit the experimental data. The pressure-temperature-concentration (P-T-X) diagrams of the pairs are also presented. It was found that ACF (A-20)/ethanol pair has considerably higher adsorption capacity than ACF (A-15)/ethanol pair. As combined heat and mass transfer plays the most important role on adsorption/desorption processes, the effect of the adsorbent bed apparent density on the adsorption rate is also studied, Experimental results show that the high apparent density improves the adsorption capacity per unit volume of the adsorber which may lead to the design a compact adsorption unit. (c) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:859 / 865
页数:7
相关论文
共 15 条
[1]   Design, construction and test run of a solid adsorption solar refrigerator using activated carbon/methanol, as adsorbent/adsorbate pair [J].
Anyanwu, EE ;
Ezekwe, CI .
ENERGY CONVERSION AND MANAGEMENT, 2003, 44 (18) :2879-2892
[2]  
Boelman EC, 1995, ASHRAE TRAN, V101, P358
[3]   Environmentally benign working pairs for adsorption refrigeration [J].
Cui, Q ;
Tao, G ;
Chen, HJ ;
Guo, XY ;
Yao, HQ .
ENERGY, 2005, 30 (2-4) :261-271
[4]  
Dubinin M.M., 1975, Progress In Surface And Membrane Science, V9, P1, DOI [10.1016/B978-0-12-571809-7.50006-1, DOI 10.1016/B978-0-12-571809-7.50006-1]
[5]  
Jing H., 1993, Renewable Energy, V3, P567, DOI 10.1016/0960-1481(93)90062-L
[6]   Production of cold heat energy by alcohol/activated carbon adsorption heat pump with a disk-module-type adsorber [J].
Kanamori, M ;
Hiramatsu, M ;
Katsurayama, K ;
Watanabe, F ;
Matsuda, H ;
Hasatani, M .
JOURNAL OF CHEMICAL ENGINEERING OF JAPAN, 1997, 30 (03) :434-439
[7]  
Saha B. B., 2002, P AS C REFR AIR COND, P353
[8]   Performance evaluation of a low-temperature waste heat driven multi-bed adsorption chiller [J].
Saha, BB ;
Koyama, S ;
Lee, JB ;
Kuwahara, K ;
Alam, KCA ;
Hamamoto, Y ;
Akisawa, A ;
Kashiwagi, T .
INTERNATIONAL JOURNAL OF MULTIPHASE FLOW, 2003, 29 (08) :1249-1263
[9]  
Saha BB, 1995, ASHRAE TRAN, V101, P348
[10]   Advanced solid sorption air conditioning modules using monolithic carbon-ammonia pair [J].
Tamainot-Telto, Z ;
Critoph, RE .
APPLIED THERMAL ENGINEERING, 2003, 23 (06) :659-674