Dynamic simulation of building VAV air-conditioning system and evaluation of EMCS on-line control strategies

被引:121
作者
Wang, SW [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Peoples R China
关键词
D O I
10.1016/S0360-1323(98)00052-3
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Dynamic models are developed to simulate the thermal, hydraulic, environmental and mechanic characteristics and energy performance of a building and VAV air-conditioning system under the control of EMCS. Three on-line supervisory strategies and programs based on integrated EMCS stations are developed to optimise the VAV static pressure set-point, AHU outlet air temperature set-point and outdoor ventilation air flow set-point, The strategies and programs are commissioned and evaluated under the simulated 'real-life' environment. This paper presents the dynamic models, the control strategies and the simulation exercises for commissioning and evaluation of the strategies. (C) 1999 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:681 / 705
页数:25
相关论文
共 22 条
[1]  
*ASHRAE, 1996, 621989R ASHRAE
[2]  
Beckman, 1994, INDOOR ENVIRON, V3, P331
[3]  
COAD W, 1996, INDOOR AIR QUALITY D
[4]  
CRRADO V, 1991, 17 IEA POL TOR
[5]  
ENGLANDER SL, 1993, ASHRAE T, V100
[6]  
HAVES P, 1989, P BUILD 1989 IBPSA V
[7]  
HOLMES M, 275 BSRIA
[8]  
House JM, 1995, ASHRAE TRAN, V101, P647
[9]  
JANU GJ, 1995, ASHRAE J APR
[10]  
KLEIN SA, 1990, TRNSYS TRANSIENT SIM