A Two-Stage Robust Reactive Power Optimization Considering Uncertain Wind Power Integration in Active Distribution Networks

被引:409
作者
Ding, Tao [1 ]
Liu, Shiyu [1 ]
Yuan, Wei [2 ]
Bie, Zhaohong [1 ]
Zeng, Bo [2 ]
机构
[1] Xi An Jiao Tong Univ, Dept Elect Engn, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
[2] Univ S Florida, Dept Ind & Management Syst Engn, Tampa, FL 33613 USA
基金
中国国家自然科学基金;
关键词
Active distribution network; column-and-constraint generation algorithm; reactive power optimization; two-stage robust optimization; wind power; PARTICLE SWARM OPTIMIZATION; FLOW MODEL RELAXATIONS; VOLTAGE CONTROL; SYSTEM; MANAGEMENT; ALGORITHM; DISPATCH;
D O I
10.1109/TSTE.2015.2494587
中图分类号
X [环境科学、安全科学];
学科分类号
083001 [环境科学];
摘要
Traditional reactive power optimization aims to minimize the total transmission losses by control reactive power compensators and transformer tap ratios, while guaranteeing the physical and operating constraints, such as voltage magnitudes and branch currents to be within their reasonable range. However, large amounts of renewable resources coming into power systems bring about great challenges to traditional planning and operation due to the stochastic nature. In most of the practical cases from China, the wind farms are centrally integrated into active distribution networks. By the use of conic relaxation based branch flow formulation, the reactive optimization problem in active distribution networks can be formulated as a mixed integer convex programming model that can be tractably dealt with. Furthermore, to address the uncertainties of wind power output, a two-stage robust optimization model is proposed to coordinate the discrete and continuous reactive power compensators and find a robust optimal solution that can hedge against any possible realization within the uncertain wind power output. Moreover, the second order cone programming-based column-and-constraint generation algorithm is employed to solve the proposed two-stage robust reactive power optimization model. Numerical results on 33-, 69- and 123-bus systems and comparison with the deterministic approach demonstrate the effectiveness of the proposed method.
引用
收藏
页码:301 / 311
页数:11
相关论文
共 33 条
[1]
FURTHER DEVELOPMENTS IN LP-BASED OPTIMAL POWER FLOW [J].
ALSAC, O ;
BRIGHT, J ;
PRAIS, M ;
STOTT, B .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1990, 5 (03) :697-711
[2]
OPTIMAL VAR PLANNING BY APPROXIMATION METHOD FOR RECURSIVE MIXED-INTEGER LINEAR-PROGRAMMING [J].
AOKI, K ;
FAN, M ;
NISHIKORI, A .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1988, 3 (04) :1741-1747
[3]
Multi-objective VAr planning for large-scale power systems using projection-based two-layer simulated annealing algorithms [J].
Chen, YL ;
Ke, YL .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2004, 151 (04) :555-560
[4]
CORSI S, 1995, IEEE T POWER SYST, V10, P686, DOI 10.1109/59.387904
[5]
Seeker Optimization Algorithm for Optimal Reactive Power Dispatch [J].
Dai, Chaohua ;
Chen, Weirong ;
Zhu, Yunfang ;
Zhang, Xuexia .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2009, 24 (03) :1218-1231
[6]
LINEAR REACTIVE POWER OPTIMIZATION IN A LARGE POWER NETWORK USING THE DECOMPOSITION APPROACH [J].
DEEB, N ;
SHAHIDEHPOUR, SM .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1990, 5 (02) :428-478
[7]
A heuristic and algorithmic combined approach for reactive power optimization with time-varying load demand in distribution systems [J].
Deng, YM ;
Ren, XJ ;
Zhao, CC ;
Zhao, DP .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2002, 17 (04) :1068-1072
[8]
Ding T., 2015, IEEE T SMAR IN PRESS
[9]
Interval radial power flow using extended DistFlow formulation and Krawczyk iteration method with sparse approximate inverse preconditioner [J].
Ding, Tao ;
Li, Fangxing ;
Li, Xue ;
Sun, Hongbin ;
Bo, Rui .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2015, 9 (14) :1998-2006
[10]
A Bi-Level Branch and Bound Method for Economic Dispatch With Disjoint Prohibited Zones Considering Network Losses [J].
Ding, Tao ;
Bo, Rui ;
Li, Fangxing ;
Sun, Hongbin .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (06) :2841-2855