A critical investigation into the heat and mass transfer analysis of counterflow wet-cooling towers

被引:183
作者
Kloppers, JC
Kröger, DG
机构
[1] Sasol Technol Pty Ltd, ZA-2302 Secunda, South Africa
[2] Univ Stellenbosch, Dept Engn Mech, ZA-7600 Stellenbosch, South Africa
关键词
D O I
10.1016/j.ijheatmasstransfer.2004.09.004
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study gives a detailed derivation of the heat and mass transfer equations of evaporative cooling in wet-cooling towers. The governing equations of the rigorous Poppe method of analysis are derived from first principles. The method of Poppe is well suited for the analysis of hybrid cooling towers as the state of the outlet air is accurately predicted. The governing equations of the Merkel method of analysis are subsequently derived after some simplifying assumptions are made. The equations of the effectiveness-NTU method applied to wet-cooling towers are also presented. The governing equations of the Poppe method are extended to give a more detailed representation of the Merkel number. The differences in the heat and mass transfer analyses and solution techniques of the Merkel and Poppe methods are described with the aid of enthalpy diagrams and psychrometric charts. The psychrometric chart is extended to accommodate air in the supersaturated state. (C) 2004 Elsevier Ltd. All rights reserved.
引用
收藏
页码:765 / 777
页数:13
相关论文
共 26 条
[1]  
[Anonymous], 1988, 4485 BRIT STAND
[2]  
BAARD TW, 1998, PERFORMANCE CHARACTE
[3]  
BAKER DR, 1961, T ASME, P339
[4]  
BERMAN LD, 1961, EVAPORATIVE COOLING, P94
[5]  
Bosnjakovic F., 1965, Technische Thermodinamik
[6]  
BOURILLOT C, 1983, EPRI REP CS3144 SR
[7]  
Bourillot C., 1983, CS3212SR EPRI
[8]  
Burden RL, 1997, NUMERICAL ANAL
[9]  
*CTI, 1997, ATC105, V1
[10]  
*CTI, 1967, COOL TOW PERF CURV