System efficiency of a DC/DC converter-based wind farm

被引:60
作者
Max, Lena [1 ]
Lundberg, Stefan [1 ]
机构
[1] Chalmers, Dept Energy & Environm, SE-41296 Gothenburg, Sweden
关键词
DC wind farm; DC/DC converters; loss calculations;
D O I
10.1002/we.259
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this paper, three DC/DC converter topologies are evaluated from an energy efficiency point of view regarding their suitability for the application in a DC wind farm grid. The three investigated topologies are the fullbridge (FB) converter, the single active bridge (SAB) converter and the series parallel resonant (LCC) converter. The energy efficiency of the three converter topologies is evaluated for different control strategies. It is found that the LCC and FB converters have the lowest losses of the three topologies. It is also shown that the wide range of operation creates problems for all three converters. The SAB converter has the largest increase in losses caused by the wide range of operation. The FB converter also has an increase in losses for this variable operating range, whereas the LCC converter has large stresses for the input and output filters. By considering some further factors, such as the contribution to the energy production cost, the design and the control of the converters, the FB converter is found to be a suitable choice for wind farm application. Copyright (C) 2007 John Wiley & Sons, Ltd.
引用
收藏
页码:109 / 120
页数:12
相关论文
共 16 条
[1]   New high power dc-dc converter with loss limited switching and lossless secondary clamp [J].
Bendre, A ;
Norris, S ;
Divan, D ;
Wallace, I ;
Gascoigne, RW .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2003, 18 (04) :1020-1027
[2]  
Demetriades G., 2005, SMALL SIGNAL ANAL CO
[3]  
DEMETRIADES GD, 2001, EVALUATION DIFFERENT
[4]  
DESILVA DIM, 2004, IEEE PESC AACH GERM, V4, P2950
[5]  
ERICKSON RW, 2002, FUNDAMENTALS POWER E
[6]  
Johnson G.L., 1985, Wind Energy Systems
[7]   Switching frequency limit for soft-switching MF transformer system for AC-fed traction [J].
Kjellqvist, T ;
Norrga, S ;
Östlund, S .
2005 IEEE 36TH POWER ELECTRONIC SPECIALISTS CONFERENCE (PESC), VOLS 1-3, 2005, :1678-1684
[8]  
Lundberg S., 2003, 474L CHALM U TECHN
[9]  
MAX L, 2007, ENERGY EVALUATION DC
[10]  
MAX L, 2006, NORD WORKSH POW IND