A time-domain procedure for locating switched capacitors in power distribution systems

被引:23
作者
Kim, J [1 ]
Grady, WM
Arapostathis, A
Soward, JC
Bhatt, SC
机构
[1] Univ Texas, Dept Elect & Comp Engn, Austin, TX 78712 USA
[2] TXU Elect, Ft Worth, TX USA
[3] Elect Power Res Inst, Palo Alto, CA 94303 USA
关键词
backward Kalman filter; capacitor switching; power quality; switched capacitor estimation;
D O I
10.1109/TPWRD.2002.805103
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper develops a method using transient voltage and current measurements at the substation to determine which capacitor in a multicapacitor feeder switched on to cause a measured transient. The procedure is based upon time-domain analysis where a backward Kalman filter estimates the initial voltage of all feeder capacitors, and those estimates indicate which capacitor switched. The result is an automated procedure that can help electric utilities determine if their capacitors are switching properly, and also help pinpoint the source of capacitor switching-related power-quality problems.
引用
收藏
页码:1044 / 1049
页数:6
相关论文
共 11 条
[2]   DYNAMIC STATE ESTIMATION OF POWER-SYSTEM HARMONICS USING KALMAN FILTER METHODOLOGY [J].
BEIDES, HM ;
HEYDT, GT .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (04) :1663-1670
[3]  
Coury DV, 1998, INT C HARMON QUAL PO, P292, DOI 10.1109/ICHQP.1998.759902
[4]   HARMONICS AND TRANSIENT OVERVOLTAGES DUE TO CAPACITOR SWITCHING [J].
GIRGIS, AA ;
FALLON, CM ;
RUBINO, JCP ;
CATOE, RC .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1993, 29 (06) :1184-1188
[5]   Application of distribution system capacitor banks and their impact on power quality [J].
Grebe, TE .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1996, 32 (03) :714-719
[6]   Identification and tracking of harmonic sources in a power system using a Kalman filter [J].
Ma, HL ;
Girgis, AA .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (03) :1659-1665
[7]   CHARACTERISTICS AND MEASUREMENT OF CAPACITOR SWITCHING AT MEDIUM VOLTAGE DISTRIBUTION LEVEL [J].
MCCOY, CE ;
FLORYANCIC, BL .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1994, 30 (06) :1480-1489
[8]   IMPACT OF UTILITY SWITCHED CAPACITORS ON CUSTOMER SYSTEMS .2. ADJUSTABLE-SPEED DRIVE CONCERNS [J].
MCGRANAGHAN, MF ;
GREBE, TE ;
HENSLEY, G ;
SINGH, T ;
SAMOTYJ, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (04) :1623-1628
[9]   IMPACT OF UTILITY SWITCHED CAPACITORS ON CUSTOMER SYSTEMS - MAGNIFICATION AT LOW-VOLTAGE CAPACITORS [J].
MCGRANAGHAN, MF ;
ZAVADIL, RM ;
HENSLEY, G ;
SINGH, T ;
SAMOTYJ, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (02) :862-868
[10]  
Parsons AC, 1998, INT C HARMON QUAL PO, P693, DOI 10.1109/ICHQP.1998.760129