An experimental investigation of heat transfer and friction losses of interrupted and wavy fins for fin-and-tube heat exchangers

被引:72
作者
Lozza, G [1 ]
Merlo, U
机构
[1] Politecn Milan, Dipartimento Energet, I-20133 Milan, Italy
[2] Luve Contardo, I-20140 Uboldo, VA, Italy
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2001年 / 24卷 / 05期
关键词
heat transfer; air; finned tube; fin; geometry; test rig;
D O I
10.1016/S0140-7007(00)00035-9
中图分类号
O414.1 [热力学];
学科分类号
摘要
The present paper discusses the results of an extensive investigation about the performance of various fin configurations, carried out in the Luve Contardo experimental facilities and aimed to enhance the heat transfer capabilities of air-cooled condensers and liquid coolers. Test results here discussed are relative to 15 coil prototypes, having the same tube and fin geometry (25 x 21.65 mm staggered 5/8 " tube banks, 2 mm fin spacing) but different fin surface geometry, from flat to wavy to louvered to "winglet". Different rates of heat transfer and pressure loss enhancement were obtained, also depending on the quality of the pressing process. General approaches to evaluate the "goodness" of one fin design with respect to another one provided questionable results: pressure loss influence on the air flow cannot be properly evaluated unless the actual fan head curve and the coil dimensions (front area and rows number) are stipulated. The. performance of air-cooled condensers was therefore predicted and compared, for various fin design and for coil arrangements of practical interest. The type of fin adopted strongly influences the heat exchanger performance and louvered fins generally provide the best results. (C) 2001 Elsevier Science Ltd and IIR. All rights reserved.
引用
收藏
页码:409 / 416
页数:8
相关论文
共 12 条
[1]  
BIWAS G, 1994, INT J HEAT MASS TRAN, V37, P283
[2]  
GNIELINSKI V, 1976, INT CHEM ENG, V16, P359
[3]   EXPERIMENTS ON TRANSFER CHARACTERISTICS OF A CORRUGATED FIN AND TUBE HEAT-EXCHANGER CONFIGURATION [J].
GOLDSTEIN, L ;
SPARROW, EM .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1976, 98 (01) :26-34
[4]  
Hong K.T., 1996, HVACR Res, V2, P27, DOI [10.1080/10789609-1096/10301331, DOI 10.1080/10789609-1096/10301331, 10.1080/10789669.1996.10391331, DOI 10.1080/10789669.1996.10391331]
[5]   Effect of strip location on the air-side pressure drop and heat transfer in strip fin-and-tube heat exchanger [J].
Kang, HC ;
Kim, MH .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1999, 22 (04) :302-312
[6]   HEAT-TRANSFER CHARACTERIZATION OF PLATE FIN-TUBE HEAT-EXCHANGERS [J].
KAYANSAYAN, N .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1994, 17 (01) :49-57
[7]  
SHAH RK, 1985, HDB HEAT TRANSFER AP
[8]  
TANAKA T, 1984, B JSME, V27, P219
[9]   An investigation of the airside performance of the slit fin-and-tube heat exchangers [J].
Wang, CC ;
Tao, WH ;
Chang, CJ .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1999, 22 (08) :595-603
[10]   An experimental study of heat transfer and friction characteristics of typical louver fin-and-tube heat exchangers [J].
Wang, CC ;
Chi, KY ;
Chang, YJ ;
Chang, YP .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1998, 41 (4-5) :817-822