The influence of tunnel geometry and ventilation on the heat release rate of a fire

被引:89
作者
Carvel, RO
Beard, AN
Jowitt, PW
Drysdale, DD
机构
[1] Heriot Watt Univ, Sch Built Environm, Edinburgh EH14 4AS, Midlothian, Scotland
[2] Univ Edinburgh, Inst Infrastruct & Environm, Edinburgh EH9 3JN, Midlothian, Scotland
基金
英国工程与自然科学研究理事会;
关键词
tunnel fires; heat release rate; tunnel geometry; longitudinal ventilation;
D O I
10.1023/B:FIRE.0000003313.97677.c5
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
It has occasionally been observed that fires in tunnels appear to be significantly more severe than fires in the open air. A literature review has been carried out, comparing heat release data from fires in tunnels with heat release data from similar fires in the open air. A Bayesian methodology has been used to investigate the geometrical factors that have the greatest influence on heat release rate. It is shown that the heat release rate of a fire in a tunnel is influenced primarily by the width of a tunnel; a fire will tend to have a higher heat release rate in a narrow tunnel rather than in a wide tunnel. The observed relationship between heat release rate and tunnel width is presented. Results from a study investigating the variation of heat release rate with ventilation velocity for fires in tunnels are also presented. A method for making realistic estimates of the heat release rates of fires in tunnels, based on these results, is presented.
引用
收藏
页码:5 / 26
页数:22
相关论文
共 32 条
  • [1] Allison R., 1997, INQUIRY FIRE HEAVY G
  • [2] ANG AHS, 1975, PROBABILITY CONCEPTS, V1, P329
  • [3] [Anonymous], 1995, MEMORIAL TUNNEL FIRE
  • [4] [Anonymous], [No title captured]
  • [5] APTE VB, 1991, FIR SAF SCI P 3 INT, P425
  • [6] ESTIMATING LARGE POOL FIRE BURNING RATES
    BABRAUSKAS, V
    [J]. FIRE TECHNOLOGY, 1983, 19 (04) : 251 - 261
  • [7] HEAT RELEASE RATE - THE SINGLE MOST IMPORTANT VARIABLE IN FIRE HAZARD
    BABRAUSKAS, V
    PEACOCK, RD
    [J]. FIRE SAFETY JOURNAL, 1992, 18 (03) : 255 - 272
  • [8] A Bayesian estimation of the effect of forced ventilation on a pool fire in a tunnel
    Carvel, RO
    Beard, AN
    Jowitt, PW
    [J]. CIVIL ENGINEERING AND ENVIRONMENTAL SYSTEMS, 2001, 18 (04) : 279 - 302
  • [9] Variation of heat release rate with forced longitudinal ventilation for vehicle fires in tunnels
    Carvel, RO
    Beard, AN
    Jowitt, PW
    Drysdale, DD
    [J]. FIRE SAFETY JOURNAL, 2001, 36 (06) : 569 - 596
  • [10] Casale E., 1994, P INT C FIR TUNN BOR, P37