Volt/VAr control in distribution systems using a time-interval based approach

被引:108
作者
Hu, Z [1 ]
Wang, X
Chen, H
Taylor, GA
机构
[1] Xi An Jiao Tong Univ, Elect Power Engn Dept, Xian 710049, Peoples R China
[2] Brunel Univ, Brunel Inst Power Syst, Uxbridge UB8 3PH, Middx, England
关键词
D O I
10.1049/ip-gtd:20030562
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A strategy for volt/VAr control in distribution systems is described. The aim is to determine optimum dispatch schedules for on-load tap changer (OLTC) settings at substations and all shunt capacitor switching based on the day-ahead load forecast. To reduce switching operations for OLTC at substations, a time-interval based control strategy is adopted that decomposes a daily load forecast into several sequential load levels. A genetic algorithm based procedure is used to determine both the load level partitioning and the dispatch scheduling. The proposed strategy minimises the power loss and improves the voltage profile for a whole day across the whole system, whilst ensuring that the number of switching operations is less than the maximum daily allowance. A comparison of numerical studies and their associated results illustrates both the feasibility and the effectiveness of the proposed strategy.
引用
收藏
页码:548 / 554
页数:7
相关论文
共 6 条