Characterizing the diverter switch of a load tap changer in a transformer using wavelet and modal analysis

被引:9
作者
Rivas-Trujillo, Edwin [2 ]
Laniado-Jacome, Edwin [1 ]
Luis San-Roman, Jose [1 ]
Diaz, Vicente [1 ]
机构
[1] Univ Carlos III Madrid, Dept Mech Engn, E-28903 Getafe, Spain
[2] Univ Distrital, Dept Elect Engn, Bogota, Colombia
关键词
OLTC; Vibration modes; Hilbert transform; Wavelet transform; Natural frequencies; IDENTIFICATION;
D O I
10.1016/j.engstruct.2010.05.020
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Vibration analysis is a promising technique in the diagnosis of the OLTC in power transformers. In this paper the vibration modes of the natural frequencies of the diverter switch cylinder, the head, and the disc of the moving contact of an OLTC in good condition are obtained by modal analysis of the numerical model. The obtained frequencies are identified with real vibration signal analysis recorded with a mono-axial piezoelectric accelerometer on a vertical axis. The actual vibration signals were processed using a Hilbert transform and a discrete wavelet transform. This article proposes using the natural frequencies of the modes of vibration calculated for the numerical model of 3 OLCT elements as the pattern for identification of the frequencies generated in the analysis of the experimental vibration signal. The diverter switch cylinder, the head, and the disc of the moving contact of an OLTC were designed in commercial software SolidWorks (TM). Natural frequencies were analyzed using a numerical model with commercial software of the finite element method (MEF) Algor (TM) with 6 degrees of freedom (DOF) at each node. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:3011 / 3017
页数:7
相关论文
共 19 条
[1]  
[Anonymous], 1983, Electra, P21
[2]   A hilbert transform approach in source identification via multiple-input single-output modeling for correlated inputs [J].
Bae, BK ;
Kim, KJ .
MECHANICAL SYSTEMS AND SIGNAL PROCESSING, 1998, 12 (04) :501-513
[3]   Status and trends in transformer monitoring [J].
Bengtsson, C .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (03) :1379-1384
[4]   THE SIGNATURE ANALYSIS OF SONIC BEARING VIBRATIONS [J].
BRAUN, SG .
IEEE TRANSACTIONS ON SONICS AND ULTRASONICS, 1980, 27 (06) :317-328
[5]  
Brautigam S., 2001, EXPERT REV MOL MED, V1/2001, P1
[6]  
CHERNICK M, 2003, INTRO BIOSTATISTICS, P252
[7]  
Chui C. K., 1992, WAVELET ANAL ITS APP
[8]  
Du YC, 2009, IEEE IMTC P, P135
[9]   Interval natural frequency and mode shape analysis for truss structures with interval parameters [J].
Gao, W .
FINITE ELEMENTS IN ANALYSIS AND DESIGN, 2006, 42 (06) :471-477
[10]   Condition assessment of power transformer onload tap changers using wavelet analysis and self-organizing map: Field evaluation [J].
Kang, P ;
Birtwhistle, D .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (01) :78-84