Lessons learned in using ohmic techniques for battery monitoring

被引:6
作者
Bose, CSC [1 ]
Wilkins, D [1 ]
McCluer, S [1 ]
Model, MJ [1 ]
Ledgerwood, G [1 ]
机构
[1] Lucent Technol Power Syst, Mesquite, TX 75149 USA
来源
SIXTEENTH ANNUAL BATTERY CONFERENCE ON APPLICATIONS AND ADVANCES | 2001年
关键词
D O I
10.1109/BCAA.2001.905107
中图分类号
O646 [电化学、电解、磁化学];
学科分类号
081704 ;
摘要
A joint study was conducted by Lucent Technologies Power Systems and Sprint on the use of ohmic meters in predicting the state of health for VRLA batteries. The first part of the results of the study have been presented in an earlier paper [1]. The second part of the results is presented in this paper, where the effects such as the inter cell connectors, the string size and the number of parallel strings on the online battery ohmic value are studied. These effects can have profound influence on the measured values and can lead to erroneous conclusions in determining the state of the health of the batteries. Although ohmic techniques are being used widely in screening the state of health condition of battery, there is no industry standard in using the technique.
引用
收藏
页码:99 / 104
页数:6
相关论文
共 6 条
[1]  
ALBER G, P INT 1994 VANC CAN, P245
[2]  
CHALASANI SC, 2001, BATTCON 2001 MAY
[3]   UPDATED STATUS OF CONDUCTANCE CAPACITY CORRELATION STUDIES TO DETERMINE THE STATE-OF-HEALTH OF AUTOMOTIVE AND STANDBY LEAD-ACID-BATTERIES [J].
FEDER, DO ;
HLAVAC, MJ ;
MCSHANE, SJ .
JOURNAL OF POWER SOURCES, 1994, 48 (1-2) :135-161
[4]  
HAWKINS M, P INT 1995 HAG NETH, P271
[5]  
MARKLE GJ, P INT 1993 PAR FRANC, P23
[6]  
WATERS AR, P INTELEC97 MELB AUS, P675