Voltage sags: Their impact on the utility and industrial customers

被引:74
作者
Melhorn, CJ [1 ]
Davis, TD
Beam, GE
机构
[1] Electrotek Concepts Inc, Knoxville, TN 37923 USA
[2] AT&T Bell Labs, Ctr Solid State Technol, Breinigsville, PA 18031 USA
[3] Penn Power & Light, Allentown, PA 18101 USA
关键词
energy storage; lightning; power quality; voltage interruptions; voltage sags;
D O I
10.1109/28.673725
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper describes the impact of voltage Sags on the utility and industrial customers. Several utility measures are presented to minimize the customer's exposure to voltage sags. These measures cannot completely eliminate the impact of voltage sags on sensitive equipment, however. A case study is presented in this paper that includes measurement results that were used to characterize the voltage sags experienced on the utility system and in the industrial facility, Simulation results used to develop "area-of-vulnerability curves" for the industrial facility, mitigation equipment that was employed to improve the sensitive equipment's ridethrough capability, and the lessons learned from the systems approach analysis are presented.
引用
收藏
页码:549 / 558
页数:10
相关论文
共 12 条
  • [1] BEAM GE, 1993 PQA C SAN DIEG
  • [2] Bewley L. V., 1951, Traveling Waves on Transmission Systems
  • [3] CONRAD LE, 1993, 193 IEEE PSI EN
  • [4] DORR DS, 1992, POWER QUALITY MAG, V3, P8
  • [5] *EPRI, 1994, IN103251 EPRI, P1
  • [6] HUGHES BM, 1991, 1991 IEEE IAS ANN M, P1556
  • [7] *IEEE, 1994, 1159 IEEE
  • [8] *IEEE, 1987, 446 IEEE ANSI
  • [9] *IEEE, 1992, 1100 IEEE, P47
  • [10] *IEEE, 1994 IEEE IAS I CPS, P261