Application of Electromagnetic Transient-Transient Stability Hybrid Simulation to FIDVR Study

被引:55
作者
Huang, Qiuhua [1 ]
Vittal, Vijay [1 ]
机构
[1] Arizona State Univ, Dept Elect Comp & Energy Engn, Tempe, AZ 85281 USA
基金
美国国家科学基金会;
关键词
Electromagnetic transient; fault induced delayed voltage recovery; hybrid simulation; interaction protocol; multiport three-phase Thevenin equivalent; transient stability;
D O I
10.1109/TPWRS.2015.2479588
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper deals with the development of a new electromagnetic transient (EMT)-transient stability (TS) hybrid simulation platform and its application to a detailed fault-induced delayed voltage recovery (FIDVR) study on the WECC system. A new EMT-TS hybrid simulation platform, which integrates PSCAD/EMTDC and the open source power system simulation software InterPSS has been developed. A combined interaction protocol with an automatic protocol switching control scheme is proposed. A multi-port three-phase Thevenin equivalent is developed for representing an external network in an EMT simulator. Correspondingly, the external network is represented in three-sequence, and a three-sequence TS simulation algorithm is developed. These techniques allow simulation of unsymmetrical faults within the internal network without the constraint of phase balance at the boundary. The effectiveness of the proposed techniques is first tested on the IEEE 9-bus system. Subsequently, the proposed hybrid simulation approach is applied to a detailed FIDVR study on a large WECC system. The study shows that a normally cleared single-line-to-ground (SLG) fault in the transmission system could lead to an FIDVR event, with compressor motors of the air conditioning units on the faulted phases stalling first, followed by a propagation of motor stalling to the unfaulted phase. Moreover, similar events are observed in simulations with a wide range of load compositions. Lastly, the effect of the point-on-wave (POW) at which a fault is applied on the occurrence of an FIVDR event is also analyzed.
引用
收藏
页码:2634 / 2646
页数:13
相关论文
共 23 条
[1]  
Anderson GWJ, 1995, PROCEEDINGS OF EMPD '95 - 1995 INTERNATIONAL CONFERENCE ON ENERGY MANAGEMENT AND POWER DELIVERY, VOLS 1 AND 2, AND SUPPLEMENT, P462, DOI 10.1109/EMPD.1995.500772
[2]  
[Anonymous], 2009, TECHN REF PAP FAULT
[3]  
[Anonymous], 2012, PROC 10 IET INT C AC
[4]  
[Anonymous], 2002, POWER SYSTEM CONTROL
[5]   Frequency-Adaptive Power System Modeling for Multiscale Simulation of Transients [J].
Gao, Feng ;
Strunz, Kai .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2009, 24 (02) :561-571
[6]   COMPUTATION OF AC-DC SYSTEM DISTURBANCES .1. INTERACTIVE COORDINATION OF GENERATOR AND CONVERTER TRANSIENT MODELS [J].
HEFFERNAN, MD ;
TURNER, KS ;
ARRILLAGA, J ;
ARNOLD, CP .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (11) :4341-4348
[7]   Interfacing Techniques for Transient Stability and Electromagnetic Transient Programs [J].
Jalili-Marandi, V. ;
Dinavahi, V. ;
Strunz, K. ;
Martinez, J. A. ;
Ramirez, A. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (04) :2385-2395
[8]  
Kersting W. H., 2006, DISTRIBUTION SYSTEM, P52
[9]  
Kosterev D., 2008, IEEE POWER ENG SOC G, P1, DOI DOI 10.1109/PES.2008.4596557
[10]  
Kosterev D. N., P 2006 POW SYST C EX, P576