Insulator icing test methods and procedures a position paper prepared by the IEEE task force on insulator icing test methods

被引:137
作者
Farzaneh, M
Baker, T
Bernstorf, A
Brown, K
Chisholm, WA
de Tourreil, C
Drapeau, JF
Fikke, S
George, JM
Gnandt, E
Grisham, T
Gutman, I
Hartings, R
Kremer, R
Powell, G
Rolfseng, L
Rozek, T
Ruff, DL
Shaffner, D
Sklenicka, V
Sundararajan, R
Yu, J
机构
关键词
contamination; flashover; fog; high voltage transmission; ice; insulator; snow; statistical interpretation; test methods;
D O I
10.1109/TPWRD.2003.817808
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 [电气工程]; 0809 [电子科学与技术];
摘要
Test methods for evaluating flashover voltage of ceramic and nonceramic insulators under ice, snow, and cold-fog conditions are recommended. The paper describes the procedure to be followed at various stages of an evaluation test including preparation of the test object, insulator precontamination, ice, snow, and cold-fog deposits as well as voltage applications and flashover voltage evaluation. Some relevant parameters for ice accretion, flashover voltage evaluation, artificial pollution, and power source requirements are taken from IEC 60129, IEC 60507, and IEEE Std.-4-1995 on standard techniques for high-voltage testing.
引用
收藏
页码:1503 / 1515
页数:13
相关论文
共 73 条
[1]
PERFORMANCE OF HV TRANSMISSION-LINE INSULATORS IN DESERT CONDITIONS .3. POLLUTION MEASUREMENTS AT A COASTAL SITE IN THE EASTERN REGION OF SAUDI-ARABIA [J].
AKBAR, M ;
ZEDAN, F .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (01) :429-438
[2]
[Anonymous], 1995, 4 IEEE
[3]
[Anonymous], 2000, TF330409 CIGRE, P55
[4]
[Anonymous], 1991, IEC Standard 60507
[5]
[Anonymous], 1999, 330407 CIGRE TF
[6]
A STATISTICAL-METHOD FOR EVALUATING ELECTRICAL FAILURES [J].
BARRETT, JS ;
GREEN, MA .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (03) :1524-1530
[7]
BEAUSEJOUR Y, 1999, P C IC ASS FRANC SAV
[8]
An artificial contamination method for composite insulators [J].
Besztercey, G ;
Karady, GG .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (02) :732-737
[9]
FLASHOVER TESTS OF ARTIFICIALLY ICED INSULATORS [J].
CHARNESKI, MD ;
GAIBROIS, GL ;
WHITNEY, BF .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (08) :2429-2433
[10]
FLASHOVER PERFORMANCE OF ARTIFICIALLY CONTAMINATED AND ICED LONG-ROD TRANSMISSION-LINE INSULATORS [J].
CHERNEY, EA .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (01) :46-52