A modified GWO technique based cascade PI-PD controller for AGC of power systems in presence of Plug in Electric Vehicles

被引:130
作者
Padhy, Sasmita [1 ]
Panda, Sidhartha [1 ]
Mahapatra, Srikanta [2 ]
机构
[1] VSSUT, Dept Elect Engn, Burla 768018, Odisha, India
[2] KIIT Univ, Sch Elect Engn, Bhubaneswar 751024, Odisha, India
来源
ENGINEERING SCIENCE AND TECHNOLOGY-AN INTERNATIONAL JOURNAL-JESTECH | 2017年 / 20卷 / 02期
关键词
Automatic Generation Control; Cascade PI-PD controller; Grey Wolf Optimization; Modified Grey Wolf Optimization; Plug in Electric Vehicles; LOAD FREQUENCY CONTROL; AUTOMATIC-GENERATION CONTROL; TO-GRID CONTROL; ALGORITHM; DESIGN; FILTER;
D O I
10.1016/j.jestch.2017.03.004
中图分类号
T [工业技术];
学科分类号
120111 [工业工程];
摘要
A Modified Grey Wolf Optimization (MGWO) based cascade PI-PD controller is suggested in this paper for Automatic Generation Control (AGC) of power systems in presence of Plug in Electric Vehicles (PEV). The modification in original Grey Wolf Optimization (GWO) algorithm is introduced by strategy which maintains a proper balance between exploration and exploitation stages of the algorithm and gives more importance to the fittest wolves to find the new position of grey wolves during the iterations. Proposed algorithm is first tested using four bench mark test functions and compared with original GWO, Differential Evolution (DE), Gravitational Search Algorithm (GSA), Particle Swarm Optimization (PSO) to show its superiority. The proposed technique is then used to tune various conventional controllers in a single area three-unit power system consisting of thermal hydro and gas power plants for AGC. The superiority of proposed MGWO algorithm over some recently proposed approaches has been demonstrated. In the next step, different controllers like PI, PID, and cascaded PI-PD controller are taken and Plug in Electric Vehicles (PEVs) are assumed. The proposed approach is also extended to a two-area six-unit power system. Lastly, a five unequal area nonlinear power system with PEVs and dissimilar cascade PI-PD controller in each area is considered and proposed MGWO technique is employed to optimize the controller parameters in presence of nonlinearities like rate constraint of units, dead zone of governor and communication delay. It is observed that PEVs contribute in the AGC to control system frequency. (C) 2017 Karabuk University. Publishing services by Elsevier B.V.
引用
收藏
页码:427 / 442
页数:16
相关论文
共 35 条
[1]
[Anonymous], 17 POW SYST COMP C S
[2]
[Anonymous], IEEE T POWER SYST
[3]
[Anonymous], 2009, POWER SYSTEM STABILI
[4]
Comparative performance analysis of teaching learning based optimization for automatic load frequency control of multi-source power systems [J].
Barisal, A. K. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 66 :67-77
[5]
Flower Pollination Algorithm Optimized PI-PD Cascade Controller in Automatic Generation Control of a Multi-area Power System [J].
Dash, Puja ;
Saikia, Lalit Chandra ;
Sinha, Nidul .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2016, 82 :19-28
[6]
Elgerd O.I., 2007, Electric energy systems theory: an introduction
[7]
MEGAWATT-FREQUENCY CONTROL PROBLEM - A NEW APPROACH VIA OPTIMAL CONTROL THEORY [J].
FOSHA, CE ;
ELGERD, OI .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1970, PA89 (04) :563-+
[8]
A conceptual framework for the vehicle-to-grid (V2G) implementation [J].
Guille, Christophe ;
Gross, George .
ENERGY POLICY, 2009, 37 (11) :4379-4390
[9]
TUNING OF PID CONTROLLERS BASED ON GAIN AND PHASE MARGIN SPECIFICATIONS [J].
HO, WK ;
HANG, CC ;
CAO, LS .
AUTOMATICA, 1995, 31 (03) :497-502
[10]
Economic dispatch using hybrid grey wolf optimizer [J].
Jayabarathi, T. ;
Raghunathan, T. ;
Adarsh, B. R. ;
Suganthan, Ponnuthurai Nagaratnam .
ENERGY, 2016, 111 :630-641